33 high priority and 7 medium priority items ready for review.
Controls QA Review Pack
Site issues, made visible.
A live review pack built from the latest Niagara audit exports. It turns the source reports into one clear action list, so issues can be checked, assigned, and closed without digging through every report manually.
Points with missing histories or weak evidence coverage.
After-hours runtime found in the latest runtime audit.
Normal alarms still sitting unacknowledged. Active unacked: 12.
Energy or metering issues worth checking first.
Comfort or control issues affecting how the site actually runs.
Action register
Review what matters first.
Filter the list, open the evidence, and update each item as it moves through review.
| # | Priority | Discipline | Equipment | Issue | Evidence | Recommended action | Source | Review status |
|---|---|---|---|---|---|---|---|---|
| 1 | HIGH | Controls / Mechanical | FCU_01slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 | COOLING_VALVE_HUNTING Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 30; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 1.25; Zone below setpoint hours: 0.5; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.75; Heating valve open supply not warm hours: 1.75; Cooling valve movement: 2921.0; Heating valve movement: 156.0 |
Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. |
Building Health Rollup | |
| 2 | HIGH | Controls / Mechanical | FCU_02slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 500.98; Total enabled hours: 299.98; Run while disabled hours: 214.0; Enabled not running hours: 13.0; After-hours run hours: 55.02; Total starts: 31; Average daily run hours: 16.7; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. |
Building Health Rollup | |
| 3 | HIGH | Controls / Mechanical | FCU_03slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 500.98; Total enabled hours: 506.91; Run while disabled hours: 7.11; Enabled not running hours: 13.04; After-hours run hours: 55.03; Total starts: 31; Average daily run hours: 16.7; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. |
Building Health Rollup | |
| 4 | HIGH | Controls / Mechanical | FCU_04slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 393.47; Total enabled hours: 429.96; Run while disabled hours: 53.53; Enabled not running hours: 90.02; After-hours run hours: 64.23; Total starts: 319; Average daily run hours: 13.12; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. |
Building Health Rollup | |
| 5 | HIGH | Controls / Mechanical | FCU_05slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 500.97; Total enabled hours: 506.95; Run while disabled hours: 7.08; Enabled not running hours: 13.06; After-hours run hours: 55.02; Total starts: 31; Average daily run hours: 16.7; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. |
Building Health Rollup | |
| 6 | HIGH | Controls / Mechanical | FCU_05slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05 | COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 10.5; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 26.5; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 3145.0; Heating valve movement: 0.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. |
Building Health Rollup | |
| 7 | HIGH | Controls / Mechanical | FCU_06slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 500.97; Total enabled hours: 31.83; Run while disabled hours: 469.15; Enabled not running hours: 0.0; After-hours run hours: 55.02; Total starts: 30; Average daily run hours: 16.7; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Review schedules and after-hours operation. |
Building Health Rollup | |
| 8 | HIGH | Controls / Mechanical | FCU_06slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06 | ZONE_BELOW_SETPOINT Zone temperature appears below setpoint for part of the sample period. COMFORT_CONTROL |
Thermal score: 30; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 26.25; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 3.25; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 2600.0; Heating valve movement: 0.0 |
Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. |
Building Health Rollup | |
| 9 | HIGH | Controls / Mechanical | FCU_07slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 356.47; Total enabled hours: 1.14; Run while disabled hours: 355.42; Enabled not running hours: 0.09; After-hours run hours: 12.59; Total starts: 26; Average daily run hours: 11.88; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Review schedules and after-hours operation. |
Building Health Rollup | |
| 10 | HIGH | Controls / Mechanical | FCU_07slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07 | HEATING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 0; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 30.0; Zone below setpoint hours: 24.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 1.0; Heating valve open supply not warm hours: 9.0; Cooling valve movement: 313.0; Heating valve movement: 2127.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. |
Building Health Rollup | |
| 11 | HIGH | Controls / Mechanical | FCU_08slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 367.99; Total enabled hours: 368.33; Run while disabled hours: 82.02; Enabled not running hours: 82.35; After-hours run hours: 0.0; Total starts: 30; Average daily run hours: 12.27; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. |
Building Health Rollup | |
| 12 | HIGH | Controls / Mechanical | FCU_08slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08 | SIMULTANEOUS_HEAT_COOL Heating and cooling appear to be active at the same time. COMFORT_CONTROL |
Thermal score: 20; Readiness: PARTIAL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 14.5; Heating valve open supply not warm hours: 66.5; Cooling valve movement: 774.0; Heating valve movement: 991.0 |
Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. |
Building Health Rollup | |
| 13 | HIGH | Controls / Mechanical | FCU_09slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 328.63; Total enabled hours: 367.59; Run while disabled hours: 5.26; Enabled not running hours: 44.22; After-hours run hours: 12.6; Total starts: 258; Average daily run hours: 10.95; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. |
Building Health Rollup | |
| 14 | HIGH | Controls / Mechanical | FCU_09slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09 | COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 15; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 76.75; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 2169.0; Heating valve movement: 0.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. |
Building Health Rollup | |
| 15 | HIGH | Controls / Mechanical | FCU_10slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 356.47; Total enabled hours: 367.9; Run while disabled hours: 5.37; Enabled not running hours: 16.79; After-hours run hours: 12.6; Total starts: 26; Average daily run hours: 11.88; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. |
Building Health Rollup | |
| 16 | HIGH | Controls / Mechanical | FCU_11slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 568.84; Total enabled hours: 475.41; Run while disabled hours: 100.9; Enabled not running hours: 7.46; After-hours run hours: 150.62; Total starts: 58; Average daily run hours: 18.96; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. |
Building Health Rollup | |
| 17 | HIGH | Controls / Mechanical | FCU_11slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11 | HEATING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 113.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 28.0; Cooling valve movement: 0.0; Heating valve movement: 8539.0 |
Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. |
Building Health Rollup | |
| 18 | HIGH | Controls / Mechanical | FCU_12slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_12 | COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 15; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 80.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 93.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 1200.0; Heating valve movement: 0.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. |
Building Health Rollup | |
| 19 | HIGH | Controls / Mechanical | FCU_13slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 399.61; Total enabled hours: 710.17; Run while disabled hours: 5.63; Enabled not running hours: 316.19; After-hours run hours: 39.29; Total starts: 39; Average daily run hours: 13.32; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. |
Building Health Rollup | |
| 20 | HIGH | Controls / Mechanical | FCU_13slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13 | COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 38.75; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 6891.0; Heating valve movement: 0.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. |
Building Health Rollup | |
| 21 | HIGH | Controls / Mechanical | FCU_14slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_14 | COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 167.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 8.25; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 6844.0; Heating valve movement: 0.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. |
Building Health Rollup | |
| 22 | HIGH | Controls / Mechanical | FCU_15slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15 | COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 0; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 26.25; Zone below setpoint hours: 7.5; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 14.0; Heating valve open supply not warm hours: 66.5; Cooling valve movement: 774.0; Heating valve movement: 989.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. |
Building Health Rollup | |
| 23 | HIGH | Controls / Mechanical | FCU_16slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16 | RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run. RUNTIME_OPERATION |
Total status run hours: 356.48; Total enabled hours: 368.36; Run while disabled hours: 4.91; Enabled not running hours: 16.79; After-hours run hours: 12.62; Total starts: 26; Average daily run hours: 11.88; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. |
Building Health Rollup | |
| 24 | HIGH | Controls / Mechanical | FCU_16slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16 | COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review. COMFORT_CONTROL |
Thermal score: 15; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 14.25; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 2168.0; Heating valve movement: 0.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. |
Building Health Rollup | |
| 25 | HIGH | Energy / Metering | CoGenslot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/CoGen | KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly. ENERGY_WASTE |
Energy score: 0; Period kWh: 0.0; Estimated kWh from kW: 590.87; kW/kWh difference percent: 100.0; Average kW: 3.52; Max kW: 6.5; Base load kW: 0.0; After-hours ratio: 0.93; Average power factor: 0.0; Average voltage imbalance percent: 0.51; Average current imbalance percent: 35.62 |
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. |
Building Health Rollup | |
| 26 | HIGH | Energy / Metering | DB_01slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_01 | KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly. ENERGY_WASTE |
Energy score: 0; Period kWh: 906.8; Estimated kWh from kW: 38979.25; kW/kWh difference percent: 97.67; Average kW: 232.02; Max kW: 236.3; Base load kW: 225.9; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.49; Average current imbalance percent: 0.0 |
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. |
Building Health Rollup | |
| 27 | HIGH | Energy / Metering | DB_CP_01slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_CP_01 | KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly. ENERGY_WASTE |
Energy score: 0; Period kWh: 374.4; Estimated kWh from kW: 39223.18; kW/kWh difference percent: 99.05; Average kW: 233.47; Max kW: 236.0; Base load kW: 229.7; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.46; Average current imbalance percent: 0.0 |
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. |
Building Health Rollup | |
| 28 | HIGH | Energy / Metering | DB_CP_02slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_CP_02 | KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly. ENERGY_WASTE |
Energy score: 0; Period kWh: 0.0; Estimated kWh from kW: 38935.87; kW/kWh difference percent: 100.0; Average kW: 231.76; Max kW: 234.7; Base load kW: 227.5; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.51; Average current imbalance percent: 0.0 |
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. |
Building Health Rollup | |
| 29 | HIGH | Energy / Metering | DB_Cafeslot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_Cafe | KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly. ENERGY_WASTE |
Energy score: 0; Period kWh: 6.9; Estimated kWh from kW: 39232.85; kW/kWh difference percent: 99.98; Average kW: 233.53; Max kW: 236.1; Base load kW: 229.4; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.53; Average current imbalance percent: 0.0 |
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. |
Building Health Rollup | |
| 30 | HIGH | Energy / Metering | DB_Lift_Aslot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_Lift_A | KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly. ENERGY_WASTE |
Energy score: 0; Period kWh: 77.9; Estimated kWh from kW: 54.07; kW/kWh difference percent: 30.58; Average kW: 0.32; Max kW: 5.8; Base load kW: 0.1; After-hours ratio: 0.84; Average power factor: 0.0; Average voltage imbalance percent: 0.43; Average current imbalance percent: 10.81 |
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. |
Building Health Rollup | |
| 31 | HIGH | Energy / Metering | MSSB_01slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_01 | KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly. ENERGY_WASTE |
Energy score: 0; Period kWh: 940.7; Estimated kWh from kW: 573.88; kW/kWh difference percent: 38.99; Average kW: 3.42; Max kW: 6.5; Base load kW: 0.0; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.49; Average current imbalance percent: 15.2 |
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. |
Building Health Rollup | |
| 32 | HIGH | Energy / Metering | MSSB_02slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_02 | KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly. ENERGY_WASTE |
Energy score: 0; Period kWh: 1861.2; Estimated kWh from kW: 368.35; kW/kWh difference percent: 80.21; Average kW: 2.19; Max kW: 6.6; Base load kW: 0.0; After-hours ratio: 1.18; Average power factor: 0.0; Average voltage imbalance percent: 0.54; Average current imbalance percent: 3.95 |
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. |
Building Health Rollup | |
| 33 | HIGH | Energy / Metering | MSSB_03slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_03 | KWH_ONLY_USAGE Energy audit flagged this meter for review. ENERGY_WASTE |
Energy score: 0; Period kWh: 5.8; Estimated kWh from kW: 0.0; kW/kWh difference percent: 100.0; Average kW: 0.0; Max kW: 0.0; Base load kW: 0.0; After-hours ratio: 0.0; Average power factor: 0.0; Average voltage imbalance percent: 0.29; Average current imbalance percent: 0.0 |
kWh counter increased while kW-derived usage was zero or unavailable. Check whether true power is disabled, scaled incorrectly, mapped to the wrong point, or not recording useful values. kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. |
Building Health Rollup | |
| 34 | MEDIUM | Controls / Mechanical | AHU_05slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05 | THERMAL_DATA_QUALITY Thermal audit data quality is incomplete or weak for this equipment. COMFORT_CONTROL |
Thermal score: 60; Readiness: LOW_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 0.0 |
Fallback zone setpoint is available, but zone comfort could not be calculated because zone temperature data was not usable. |
Building Health Rollup | |
| 35 | MEDIUM | Controls / Mechanical | Chiller_02slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 | THERMAL_DATA_QUALITY Thermal audit data quality is incomplete or weak for this equipment. COMFORT_CONTROL |
Thermal score: 60; Readiness: LOW_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 0.0 |
Fallback zone setpoint is available, but zone comfort could not be calculated because zone temperature data was not usable. |
Building Health Rollup | |
| 36 | MEDIUM | Controls / Mechanical | FCU_03slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03 | ZONE_ABOVE_SETPOINT Zone temperature appears above setpoint for part of the sample period. COMFORT_CONTROL |
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 0.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. |
Building Health Rollup | |
| 37 | MEDIUM | Controls / Mechanical | FCU_04slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04 | ZONE_ABOVE_SETPOINT Zone temperature appears above setpoint for part of the sample period. COMFORT_CONTROL |
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.5; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 65.0; Heating valve movement: 0.0 |
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. |
Building Health Rollup | |
| 38 | MEDIUM | Controls / Mechanical | FCU_10slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10 | ZONE_BELOW_SETPOINT Zone temperature appears below setpoint for part of the sample period. COMFORT_CONTROL |
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 138.75; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 213.0 |
Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. |
Building Health Rollup | |
| 39 | MEDIUM | Controls / Mechanical | FCU_15slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15 | ENABLED_NOT_RUNNING Equipment appears enabled but did not prove run during part of the sample. RUNTIME_OPERATION |
Total status run hours: 367.99; Total enabled hours: 718.85; Run while disabled hours: 0.26; Enabled not running hours: 351.12; After-hours run hours: 0.0; Total starts: 30; Average daily run hours: 12.27; Has status history: true; Has enable history: true |
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. |
Building Health Rollup | |
| 40 | MEDIUM | Controls / Mechanical | FCU_02slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02 | ZONE_BELOW_SETPOINT Zone temperature appears below setpoint for part of the sample period. COMFORT_CONTROL |
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 74.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.5; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 60.0; Heating valve movement: 0.0 |
Zone comfort used the fallback zone setpoint slot because no usable zone setpoint history was available. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. |
Building Health Rollup |
Review flow
Check, assign, close.
Start with the items that carry the most risk. Open the evidence when needed, confirm what is real on site, then mark the outcome clearly.
1. Check the evidence
Start with the linked source report. If the data is thin, fix the visibility problem
2. Confirm on site
Use the register to check the highest-risk runtime, comfort, alarm, energy, schedule, and network items first.
3. Track the outcome
Mark each item as reviewed, assigned, accepted, or closed
Source reports
Evidence used.
These are the reports used to build this review pack.
| Status | Audit | Stage / title | Generated | Evidence |
|---|---|---|---|---|
| Found | Discovery / History Mapping | BUILDING_INTELLIGENCE_STAGE_1_DISCOVERY_CORE | 2026-06-25T20:28:19+1000 | Open source report |
| Found | Runtime Audit | BUILDING_INTELLIGENCE_STAGE_2_RUNTIME_AUDIT | 2026-06-25T20:56:59+1000 | Open source report |
| Found | Thermal Audit | BUILDING_INTELLIGENCE_STAGE_3_THERMAL_AUDIT | 2026-06-22T10:17:28+1000 | Open source report |
| Found | Energy Audit | BUILDING_INTELLIGENCE_STAGE_4_ENERGY_AUDIT | 2026-06-25T21:12:35+1000 | Open source report |
| Found | Energy Trend Audit | BUILDING_INTELLIGENCE_STAGE_4_1_ENERGY_TREND_AUDIT | 2026-06-25T21:15:12+1000 | Open source report |
| Found | Schedule / Override Audit | BUILDING_INTELLIGENCE_STAGE_5_SCHEDULE_OVERRIDE_AUDIT | 2026-06-25T21:23:47+1000 | Open source report |
| Found | Alarm Health Audit | Alarm Health Audit | 2026-06-25T21:12:15+1000 | Open source report |
| Found | BACnet Network Health | BACnet Network and Device Health Audit | Open source report | |
| Found | Economiser Audit | BUILDING_INTELLIGENCE_STAGE_7_ECONOMISER_AUDIT | 2026-06-22T13:53:38+1000 | Open source report |
| Found | Building Health Rollup | BUILDING_INTELLIGENCE_STAGE_7_ECONOMISER_AUDIT | 2026-06-25T21:12:17+1000 | Open source report |