Controls QA Review Pack

Site issues, made visible.

A live review pack built from the latest Niagara audit exports. It turns the source reports into one clear action list, so issues can be checked, assigned, and closed without digging through every report manually.

Action Register
40

33 high priority and 7 medium priority items ready for review.

Data Readiness
109

Points with missing histories or weak evidence coverage.

Runtime / Schedules
2015.4

After-hours runtime found in the latest runtime audit.

Alarm Handling
988

Normal alarms still sitting unacknowledged. Active unacked: 12.

Energy / Metering
9

Energy or metering issues worth checking first.

Comfort / Control
14

Comfort or control issues affecting how the site actually runs.

Action register

Review what matters first.

Filter the list, open the evidence, and update each item as it moves through review.

View source reports
#PriorityDisciplineEquipmentIssueEvidenceRecommended actionSourceReview status
1 HIGH Controls / Mechanical FCU_01slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 COOLING_VALVE_HUNTING Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 30; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 1.25; Zone below setpoint hours: 0.5; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.75; Heating valve open supply not warm hours: 1.75; Cooling valve movement: 2921.0; Heating valve movement: 156.0
Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing.
Building Health Rollup
2 HIGH Controls / Mechanical FCU_02slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 500.98; Total enabled hours: 299.98; Run while disabled hours: 214.0; Enabled not running hours: 13.0; After-hours run hours: 55.02; Total starts: 31; Average daily run hours: 16.7; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation.
Building Health Rollup
3 HIGH Controls / Mechanical FCU_03slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 500.98; Total enabled hours: 506.91; Run while disabled hours: 7.11; Enabled not running hours: 13.04; After-hours run hours: 55.03; Total starts: 31; Average daily run hours: 16.7; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation.
Building Health Rollup
4 HIGH Controls / Mechanical FCU_04slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 393.47; Total enabled hours: 429.96; Run while disabled hours: 53.53; Enabled not running hours: 90.02; After-hours run hours: 64.23; Total starts: 319; Average daily run hours: 13.12; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation.
Building Health Rollup
5 HIGH Controls / Mechanical FCU_05slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 500.97; Total enabled hours: 506.95; Run while disabled hours: 7.08; Enabled not running hours: 13.06; After-hours run hours: 55.02; Total starts: 31; Average daily run hours: 16.7; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation.
Building Health Rollup
6 HIGH Controls / Mechanical FCU_05slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05 COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 10.5; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 26.5; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 3145.0; Heating valve movement: 0.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing.
Building Health Rollup
7 HIGH Controls / Mechanical FCU_06slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 500.97; Total enabled hours: 31.83; Run while disabled hours: 469.15; Enabled not running hours: 0.0; After-hours run hours: 55.02; Total starts: 30; Average daily run hours: 16.7; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Review schedules and after-hours operation.
Building Health Rollup
8 HIGH Controls / Mechanical FCU_06slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06 ZONE_BELOW_SETPOINT Zone temperature appears below setpoint for part of the sample period.
COMFORT_CONTROL
Thermal score: 30; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 26.25; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 3.25; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 2600.0; Heating valve movement: 0.0
Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing.
Building Health Rollup
9 HIGH Controls / Mechanical FCU_07slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 356.47; Total enabled hours: 1.14; Run while disabled hours: 355.42; Enabled not running hours: 0.09; After-hours run hours: 12.59; Total starts: 26; Average daily run hours: 11.88; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Review schedules and after-hours operation.
Building Health Rollup
10 HIGH Controls / Mechanical FCU_07slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07 HEATING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 0; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 30.0; Zone below setpoint hours: 24.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 1.0; Heating valve open supply not warm hours: 9.0; Cooling valve movement: 313.0; Heating valve movement: 2127.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing.
Building Health Rollup
11 HIGH Controls / Mechanical FCU_08slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 367.99; Total enabled hours: 368.33; Run while disabled hours: 82.02; Enabled not running hours: 82.35; After-hours run hours: 0.0; Total starts: 30; Average daily run hours: 12.27; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment.
Building Health Rollup
12 HIGH Controls / Mechanical FCU_08slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08 SIMULTANEOUS_HEAT_COOL Heating and cooling appear to be active at the same time.
COMFORT_CONTROL
Thermal score: 20; Readiness: PARTIAL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 14.5; Heating valve open supply not warm hours: 66.5; Cooling valve movement: 774.0; Heating valve movement: 991.0
Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing.
Building Health Rollup
13 HIGH Controls / Mechanical FCU_09slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 328.63; Total enabled hours: 367.59; Run while disabled hours: 5.26; Enabled not running hours: 44.22; After-hours run hours: 12.6; Total starts: 258; Average daily run hours: 10.95; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation.
Building Health Rollup
14 HIGH Controls / Mechanical FCU_09slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09 COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 15; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 76.75; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 2169.0; Heating valve movement: 0.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate.
Building Health Rollup
15 HIGH Controls / Mechanical FCU_10slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 356.47; Total enabled hours: 367.9; Run while disabled hours: 5.37; Enabled not running hours: 16.79; After-hours run hours: 12.6; Total starts: 26; Average daily run hours: 11.88; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation.
Building Health Rollup
16 HIGH Controls / Mechanical FCU_11slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 568.84; Total enabled hours: 475.41; Run while disabled hours: 100.9; Enabled not running hours: 7.46; After-hours run hours: 150.62; Total starts: 58; Average daily run hours: 18.96; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation.
Building Health Rollup
17 HIGH Controls / Mechanical FCU_11slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11 HEATING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 113.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 28.0; Cooling valve movement: 0.0; Heating valve movement: 8539.0
Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing.
Building Health Rollup
18 HIGH Controls / Mechanical FCU_12slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_12 COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 15; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 80.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 93.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 1200.0; Heating valve movement: 0.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate.
Building Health Rollup
19 HIGH Controls / Mechanical FCU_13slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 399.61; Total enabled hours: 710.17; Run while disabled hours: 5.63; Enabled not running hours: 316.19; After-hours run hours: 39.29; Total starts: 39; Average daily run hours: 13.32; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation.
Building Health Rollup
20 HIGH Controls / Mechanical FCU_13slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13 COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 38.75; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 6891.0; Heating valve movement: 0.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing.
Building Health Rollup
21 HIGH Controls / Mechanical FCU_14slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_14 COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 167.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 8.25; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 6844.0; Heating valve movement: 0.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing.
Building Health Rollup
22 HIGH Controls / Mechanical FCU_15slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15 COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 0; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 26.25; Zone below setpoint hours: 7.5; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 14.0; Heating valve open supply not warm hours: 66.5; Cooling valve movement: 774.0; Heating valve movement: 989.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate.
Building Health Rollup
23 HIGH Controls / Mechanical FCU_16slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16 RUNNING_WHILE_DISABLED Equipment appears to have runtime while disabled or not commanded to run.
RUNTIME_OPERATION
Total status run hours: 356.48; Total enabled hours: 368.36; Run while disabled hours: 4.91; Enabled not running hours: 16.79; After-hours run hours: 12.62; Total starts: 26; Average daily run hours: 11.88; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation.
Building Health Rollup
24 HIGH Controls / Mechanical FCU_16slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16 COOLING_NOT_EFFECTIVE Thermal audit flagged this equipment for comfort or control review.
COMFORT_CONTROL
Thermal score: 15; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 14.25; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 2168.0; Heating valve movement: 0.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate.
Building Health Rollup
25 HIGH Energy / Metering CoGenslot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/CoGen KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly.
ENERGY_WASTE
Energy score: 0; Period kWh: 0.0; Estimated kWh from kW: 590.87; kW/kWh difference percent: 100.0; Average kW: 3.52; Max kW: 6.5; Base load kW: 0.0; After-hours ratio: 0.93; Average power factor: 0.0; Average voltage imbalance percent: 0.51; Average current imbalance percent: 35.62
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
Building Health Rollup
26 HIGH Energy / Metering DB_01slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_01 KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly.
ENERGY_WASTE
Energy score: 0; Period kWh: 906.8; Estimated kWh from kW: 38979.25; kW/kWh difference percent: 97.67; Average kW: 232.02; Max kW: 236.3; Base load kW: 225.9; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.49; Average current imbalance percent: 0.0
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption.
Building Health Rollup
27 HIGH Energy / Metering DB_CP_01slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_CP_01 KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly.
ENERGY_WASTE
Energy score: 0; Period kWh: 374.4; Estimated kWh from kW: 39223.18; kW/kWh difference percent: 99.05; Average kW: 233.47; Max kW: 236.0; Base load kW: 229.7; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.46; Average current imbalance percent: 0.0
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption.
Building Health Rollup
28 HIGH Energy / Metering DB_CP_02slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_CP_02 KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly.
ENERGY_WASTE
Energy score: 0; Period kWh: 0.0; Estimated kWh from kW: 38935.87; kW/kWh difference percent: 100.0; Average kW: 231.76; Max kW: 234.7; Base load kW: 227.5; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.51; Average current imbalance percent: 0.0
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption.
Building Health Rollup
29 HIGH Energy / Metering DB_Cafeslot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_Cafe KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly.
ENERGY_WASTE
Energy score: 0; Period kWh: 6.9; Estimated kWh from kW: 39232.85; kW/kWh difference percent: 99.98; Average kW: 233.53; Max kW: 236.1; Base load kW: 229.4; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.53; Average current imbalance percent: 0.0
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption.
Building Health Rollup
30 HIGH Energy / Metering DB_Lift_Aslot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_Lift_A KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly.
ENERGY_WASTE
Energy score: 0; Period kWh: 77.9; Estimated kWh from kW: 54.07; kW/kWh difference percent: 30.58; Average kW: 0.32; Max kW: 5.8; Base load kW: 0.1; After-hours ratio: 0.84; Average power factor: 0.0; Average voltage imbalance percent: 0.43; Average current imbalance percent: 10.81
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
Building Health Rollup
31 HIGH Energy / Metering MSSB_01slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_01 KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly.
ENERGY_WASTE
Energy score: 0; Period kWh: 940.7; Estimated kWh from kW: 573.88; kW/kWh difference percent: 38.99; Average kW: 3.42; Max kW: 6.5; Base load kW: 0.0; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.49; Average current imbalance percent: 15.2
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
Building Health Rollup
32 HIGH Energy / Metering MSSB_02slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_02 KW_KWH_DISAGREE kW-derived energy and kWh counter usage disagree significantly.
ENERGY_WASTE
Energy score: 0; Period kWh: 1861.2; Estimated kWh from kW: 368.35; kW/kWh difference percent: 80.21; Average kW: 2.19; Max kW: 6.6; Base load kW: 0.0; After-hours ratio: 1.18; Average power factor: 0.0; Average voltage imbalance percent: 0.54; Average current imbalance percent: 3.95
kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
Building Health Rollup
33 HIGH Energy / Metering MSSB_03slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_03 KWH_ONLY_USAGE Energy audit flagged this meter for review.
ENERGY_WASTE
Energy score: 0; Period kWh: 5.8; Estimated kWh from kW: 0.0; kW/kWh difference percent: 100.0; Average kW: 0.0; Max kW: 0.0; Base load kW: 0.0; After-hours ratio: 0.0; Average power factor: 0.0; Average voltage imbalance percent: 0.29; Average current imbalance percent: 0.0
kWh counter increased while kW-derived usage was zero or unavailable. Check whether true power is disabled, scaled incorrectly, mapped to the wrong point, or not recording useful values. kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
Building Health Rollup
34 MEDIUM Controls / Mechanical AHU_05slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05 THERMAL_DATA_QUALITY Thermal audit data quality is incomplete or weak for this equipment.
COMFORT_CONTROL
Thermal score: 60; Readiness: LOW_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 0.0
Fallback zone setpoint is available, but zone comfort could not be calculated because zone temperature data was not usable.
Building Health Rollup
35 MEDIUM Controls / Mechanical Chiller_02slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 THERMAL_DATA_QUALITY Thermal audit data quality is incomplete or weak for this equipment.
COMFORT_CONTROL
Thermal score: 60; Readiness: LOW_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 0.0
Fallback zone setpoint is available, but zone comfort could not be calculated because zone temperature data was not usable.
Building Health Rollup
36 MEDIUM Controls / Mechanical FCU_03slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03 ZONE_ABOVE_SETPOINT Zone temperature appears above setpoint for part of the sample period.
COMFORT_CONTROL
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 0.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions.
Building Health Rollup
37 MEDIUM Controls / Mechanical FCU_04slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04 ZONE_ABOVE_SETPOINT Zone temperature appears above setpoint for part of the sample period.
COMFORT_CONTROL
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.5; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 65.0; Heating valve movement: 0.0
Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions.
Building Health Rollup
38 MEDIUM Controls / Mechanical FCU_10slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10 ZONE_BELOW_SETPOINT Zone temperature appears below setpoint for part of the sample period.
COMFORT_CONTROL
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 138.75; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 213.0
Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions.
Building Health Rollup
39 MEDIUM Controls / Mechanical FCU_15slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15 ENABLED_NOT_RUNNING Equipment appears enabled but did not prove run during part of the sample.
RUNTIME_OPERATION
Total status run hours: 367.99; Total enabled hours: 718.85; Run while disabled hours: 0.26; Enabled not running hours: 351.12; After-hours run hours: 0.0; Total starts: 30; Average daily run hours: 12.27; Has status history: true; Has enable history: true
A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment.
Building Health Rollup
40 MEDIUM Controls / Mechanical FCU_02slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02 ZONE_BELOW_SETPOINT Zone temperature appears below setpoint for part of the sample period.
COMFORT_CONTROL
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 74.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.5; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 60.0; Heating valve movement: 0.0
Zone comfort used the fallback zone setpoint slot because no usable zone setpoint history was available. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions.
Building Health Rollup

Review flow

Check, assign, close.

Start with the items that carry the most risk. Open the evidence when needed, confirm what is real on site, then mark the outcome clearly.

1. Check the evidence

Start with the linked source report. If the data is thin, fix the visibility problem

2. Confirm on site

Use the register to check the highest-risk runtime, comfort, alarm, energy, schedule, and network items first.

3. Track the outcome

Mark each item as reviewed, assigned, accepted, or closed

Source reports

Evidence used.

These are the reports used to build this review pack.

StatusAuditStage / titleGeneratedEvidence
Found Discovery / History Mapping BUILDING_INTELLIGENCE_STAGE_1_DISCOVERY_CORE 2026-06-25T20:28:19+1000 Open source report
Found Runtime Audit BUILDING_INTELLIGENCE_STAGE_2_RUNTIME_AUDIT 2026-06-25T20:56:59+1000 Open source report
Found Thermal Audit BUILDING_INTELLIGENCE_STAGE_3_THERMAL_AUDIT 2026-06-22T10:17:28+1000 Open source report
Found Energy Audit BUILDING_INTELLIGENCE_STAGE_4_ENERGY_AUDIT 2026-06-25T21:12:35+1000 Open source report
Found Energy Trend Audit BUILDING_INTELLIGENCE_STAGE_4_1_ENERGY_TREND_AUDIT 2026-06-25T21:15:12+1000 Open source report
Found Schedule / Override Audit BUILDING_INTELLIGENCE_STAGE_5_SCHEDULE_OVERRIDE_AUDIT 2026-06-25T21:23:47+1000 Open source report
Found Alarm Health Audit Alarm Health Audit 2026-06-25T21:12:15+1000 Open source report
Found BACnet Network Health BACnet Network and Device Health Audit Open source report
Found Economiser Audit BUILDING_INTELLIGENCE_STAGE_7_ECONOMISER_AUDIT 2026-06-22T13:53:38+1000 Open source report
Found Building Health Rollup BUILDING_INTELLIGENCE_STAGE_7_ECONOMISER_AUDIT 2026-06-25T21:12:17+1000 Open source report