Stage 5

Schedule / Override Audit

Readable summary of writable priority arrays, schedule state, after-hours activity, command/status mismatches, and current override conditions.

StageBUILDING_INTELLIGENCE_STAGE_5_SCHEDULE_OVERRIDE_AUDIT
Versionstage5.scheduleOverride.test.0.9
Export time2026-06-25T21:23:47+1000
Scopelocal:|station:|slot:/Drivers
Rows analysed272
HIGH
26

Items requiring immediate review.

MEDIUM
51

Items worth reviewing.

OVERRIDES
1

Priority, manual, or override-related findings.

AFTER HOURS
23

Outputs or schedules active outside configured business hours.

High-priority schedule / override findings detected

Review the top action cards first. These usually indicate critical priorities, faults, down points, active alarms, or command/status mismatches.

How to read this report

Priority is based on visible current state, writable priority array state, schedule status, and paired command/status checks. Pair assessment means the audit compared likely schedule, command, status, fault, and alarm points within the same equipment group.

Critical priority uses configured priority threshold 2.0. High priority uses configured threshold 8.0. Business hours are 7.0 to 18.0.

Top action findings

#1 RUNNING_WHILE_DISABLED_NOW

Enable | Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02/Enable
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02
Identity chwp02
Out false
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Enable false {stale}
Status Run_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic.
COMMAND_LIKE_POINT COMMAND_OUTPUT_INACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02/Enable

#2 RUNNING_WHILE_DISABLED_NOW

Run_Status | Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02/Run_Status
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02
Identity chwp02
Out true
Out status unackedAlarm
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Enable false {stale}
Status Run_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02/Run_Status

#3 RUNNING_WHILE_DISABLED_NOW

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02/Fan_Enable
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02
Identity fcu02
Out false
Out status ok
Out priority def
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable false {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16 alarmInhibit
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic.
COMMAND_LIKE_POINT COMMAND_OUTPUT_INACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02/Fan_Enable

#4 RUNNING_WHILE_DISABLED_NOW

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02/Fan_Status
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02
Identity fcu02
Out true
Out status unackedAlarm
Out priority 16 alarmInhibit
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable false {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16 alarmInhibit
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02/Fan_Status

#5 RUNNING_WHILE_DISABLED_NOW

OCC$2dSCHEDULE | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02/OCC$2dSCHEDULE
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02
Identity fcu02
Out 0
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable false {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16 alarmInhibit
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. This is a schedule output/pass-through point, not the actual Niagara schedule component.
SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE_OUTPUT_POINT_INACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02/OCC$2dSCHEDULE

#6 RUNNING_WHILE_DISABLED_NOW

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07/Fan_Enable
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07
Identity fcu07
Out false
Out status ok
Out priority def
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 1 {ok} @ 10
Command Fan_Enable false {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16 alarmInhibit
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Schedule output is active but command is off. Check schedule-to-command logic, enable chain, interlocks, or downstream override.
COMMAND_LIKE_POINT COMMAND_OUTPUT_INACTIVE RUNNING_WHILE_DISABLED_NOW SCHEDULE_ACTIVE_COMMAND_OFF
RUNNING_WHILE_DISABLED_NOW SCHEDULE_ACTIVE_COMMAND_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07/Fan_Enable

#7 RUNNING_WHILE_DISABLED_NOW

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07/Fan_Status
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07
Identity fcu07
Out true
Out status unackedAlarm
Out priority 16 alarmInhibit
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 1 {ok} @ 10
Command Fan_Enable false {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16 alarmInhibit
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Schedule output is active but command is off. Check schedule-to-command logic, enable chain, interlocks, or downstream override. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE RUNNING_WHILE_DISABLED_NOW SCHEDULE_ACTIVE_COMMAND_OFF
RUNNING_WHILE_DISABLED_NOW SCHEDULE_ACTIVE_COMMAND_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07/Fan_Status

#8 RUNNING_WHILE_DISABLED_NOW

OCC$2dSCHEDULE | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07/OCC$2dSCHEDULE
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07
Identity fcu07
Out 1
Out status ok
Out priority 10
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 1 {ok} @ 10
Command Fan_Enable false {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16 alarmInhibit
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Schedule output is active but command is off. Check schedule-to-command logic, enable chain, interlocks, or downstream override. The schedule output/pass-through point appears active outside configured business hours. Confirm whether this represents expected occupancy or an after-hours mode. This is a schedule output/pass-through point, not the actual Niagara schedule component.
SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE_OUTPUT_POINT_ACTIVE AFTER_HOURS_SCHEDULE_OUTPUT_POINT_ACTIVE RUNNING_WHILE_DISABLED_NOW SCHEDULE_ACTIVE_COMMAND_OFF
RUNNING_WHILE_DISABLED_NOW SCHEDULE_ACTIVE_COMMAND_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07/OCC$2dSCHEDULE

#9 RUNNING_WHILE_DISABLED_NOW

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/KEF_01/Fan_Enable
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/KEF_01
Identity kef01
Out false
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic.
COMMAND_LIKE_POINT COMMAND_OUTPUT_INACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/KEF_01/Fan_Enable

#10 RUNNING_WHILE_DISABLED_NOW

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/KEF_01/Fan_Status
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/KEF_01
Identity kef01
Out true
Out status unackedAlarm
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/KEF_01/Fan_Status

#11 RUNNING_WHILE_DISABLED_NOW

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05/Fan_Enable
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05
Identity ahu05
Out false
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Run_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic.
COMMAND_LIKE_POINT COMMAND_OUTPUT_INACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05/Fan_Enable

#12 RUNNING_WHILE_DISABLED_NOW

Run_Status | Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05/Run_Status
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05
Identity ahu05
Out true
Out status unackedAlarm
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Run_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05/Run_Status

#13 RUNNING_WHILE_DISABLED_NOW

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_05/Fan_Enable
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_05
Identity ef05
Out false
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic.
COMMAND_LIKE_POINT COMMAND_OUTPUT_INACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_05/Fan_Enable

#14 RUNNING_WHILE_DISABLED_NOW

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_05/Fan_Status
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_05
Identity ef05
Out true
Out status unackedAlarm
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_05/Fan_Status

#15 RUNNING_WHILE_DISABLED_NOW

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_01/Fan_Enable
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_01
Identity tef01
Out false
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic.
COMMAND_LIKE_POINT COMMAND_OUTPUT_INACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_01/Fan_Enable

#16 RUNNING_WHILE_DISABLED_NOW

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_01/Fan_Status
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_01
Identity tef01
Out true
Out status unackedAlarm
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_01/Fan_Status

#17 RUNNING_WHILE_DISABLED_NOW

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_02/Fan_Enable
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_02
Identity tef02
Out false
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic.
COMMAND_LIKE_POINT COMMAND_OUTPUT_INACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_02/Fan_Enable

#18 RUNNING_WHILE_DISABLED_NOW

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_02/Fan_Status
HIGH
Category COMMAND_STATUS_MISMATCH
Action Controls / Mechanical
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_02
Identity tef02
Out true
Out status unackedAlarm
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule
Command Fan_Enable false {stale}
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Equipment appears to be running while the command is off. Check local hand mode, controller override, feedback mapping, or failed command logic. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE RUNNING_WHILE_DISABLED_NOW
RUNNING_WHILE_DISABLED_NOW
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_02/Fan_Status

#19 POINT_DOWN

AlarmSignal | Drivers/NiagaraNetwork/Site_Y/points/LTS_High_Wall_Split/AlarmSignal
HIGH
Category ALARM_FAULT
Action Alarms / Commissioning
Confidence LOW
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/LTS_High_Wall_Split
Identity ltshighwallsplit
Out false
Out status disabled,down,stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule
Command
Status
Fault / alarm
Recommendation: Point status indicates down. Check controller/network communication or point health. Point status indicates disabled. Confirm this is intentional.
STATUS_LIKE_POINT POINT_DOWN POINT_DISABLED STATUS_OUTPUT_INACTIVE
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/LTS_High_Wall_Split/AlarmSignal

#20 FAULT_OR_ALARM_ACTIVE

GUI_Fault | Drivers/NiagaraNetwork/Site_Y/points/PHEX_01/GUI/Fault_Logic/GUI_Fault
HIGH
Category ALARM_FAULT
Action Alarms / Commissioning
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/PHEX_01/GUI/Fault_Logic
Identity faultlogic
Out true
Out status ok
Out priority 16
Active priorities 1
Highest priority 16
Highest value true
Schedule
Command
Status
Fault / alarm
Recommendation: Fault or alarm point is active. Review the active alarm condition and associated equipment. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements. A priority command appears active outside configured business hours. Review whether the point is being held on manually.
WRITABLE_POINT_FOUND STATUS_LIKE_POINT STATUS_OUTPUT_ACTIVE FAULT_OR_ALARM_ACTIVE PRIORITY_ARRAY_ACTIVE AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS_PRIORITY_ACTIVE
Priority array and schedule details
Enabled
Fallback -
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1 - {null}
Priority 2 - {null}
Priority 3 - {null}
Priority 4 - {null}
Priority 5 - {null}
Priority 6 - {null}
Priority 7 - {null}
Priority 8 - {null}
Priority 9 - {null}
Priority 10 - {null}
Priority 11 - {null}
Priority 12 - {null}
Priority 13 - {null}
Priority 14 - {null}
Priority 15 - {null}
Priority 16 true {ok}
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/PHEX_01/GUI/Fault_Logic/GUI_Fault

#21 FAULT_OR_ALARM_ACTIVE

Low_Temp_Fault | Drivers/NiagaraNetwork/Site_Y/points/PHEX_01/GUI/Fault_Logic/Low_Temp_Fault
HIGH
Category ALARM_FAULT
Action Alarms / Commissioning
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/PHEX_01/GUI/Fault_Logic
Identity faultlogic
Out true
Out status overridden
Out priority 1
Active priorities 1
Highest priority 1
Highest value true
Schedule
Command
Status
Fault / alarm
Recommendation: Fault or alarm point is active. Review the active alarm condition and associated equipment. Point status indicates overridden. Confirm this override is intentional and still required. Output appears driven from a critical priority source. Review the command source and release if not required. Priority 1 is active. Confirm this is intentional, as priority 1 should generally be reserved for emergency or critical control. A critical priority level is active. Review the writable priority array and confirm the command source. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements. A priority command appears active outside configured business hours. Review whether the point is being held on manually.
WRITABLE_POINT_FOUND STATUS_LIKE_POINT POINT_OVERRIDDEN STATUS_OUTPUT_ACTIVE FAULT_OR_ALARM_ACTIVE PRIORITY_ARRAY_ACTIVE CRITICAL_PRIORITY_ACTIVE PRIORITY_1_ACTIVE CRITICAL_OUT_PRIORITY_SOURCE AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS_PRIORITY_ACTIVE
Priority array and schedule details
Enabled
Fallback -
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1 true {ok}
Priority 2 - {null}
Priority 3 - {null}
Priority 4 - {null}
Priority 5 - {null}
Priority 6 - {null}
Priority 7 - {null}
Priority 8 - {null}
Priority 9 - {null}
Priority 10 - {null}
Priority 11 - {null}
Priority 12 - {null}
Priority 13 - {null}
Priority 14 - {null}
Priority 15 - {null}
Priority 16 - {null}
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/PHEX_01/GUI/Fault_Logic/Low_Temp_Fault

#22 FAULT_OR_ALARM_ACTIVE

GUI_Fault | Drivers/NiagaraNetwork/Site_Y/points/PHEX_02/GUI/Fault_Logic/GUI_Fault
HIGH
Category ALARM_FAULT
Action Alarms / Commissioning
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/PHEX_02/GUI/Fault_Logic
Identity faultlogic
Out true
Out status ok
Out priority 16
Active priorities 1
Highest priority 16
Highest value true
Schedule
Command
Status
Fault / alarm
Recommendation: Fault or alarm point is active. Review the active alarm condition and associated equipment. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements. A priority command appears active outside configured business hours. Review whether the point is being held on manually.
WRITABLE_POINT_FOUND STATUS_LIKE_POINT STATUS_OUTPUT_ACTIVE FAULT_OR_ALARM_ACTIVE PRIORITY_ARRAY_ACTIVE AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS_PRIORITY_ACTIVE
Priority array and schedule details
Enabled
Fallback -
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1 - {null}
Priority 2 - {null}
Priority 3 - {null}
Priority 4 - {null}
Priority 5 - {null}
Priority 6 - {null}
Priority 7 - {null}
Priority 8 - {null}
Priority 9 - {null}
Priority 10 - {null}
Priority 11 - {null}
Priority 12 - {null}
Priority 13 - {null}
Priority 14 - {null}
Priority 15 - {null}
Priority 16 true {ok}
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/PHEX_02/GUI/Fault_Logic/GUI_Fault

#23 FAULT_OR_ALARM_ACTIVE

Low_Temp_Fault | Drivers/NiagaraNetwork/Site_Y/points/PHEX_02/GUI/Fault_Logic/Low_Temp_Fault
HIGH
Category ALARM_FAULT
Action Alarms / Commissioning
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/PHEX_02/GUI/Fault_Logic
Identity faultlogic
Out true
Out status overridden
Out priority 1
Active priorities 1
Highest priority 1
Highest value true
Schedule
Command
Status
Fault / alarm
Recommendation: Fault or alarm point is active. Review the active alarm condition and associated equipment. Point status indicates overridden. Confirm this override is intentional and still required. Output appears driven from a critical priority source. Review the command source and release if not required. Priority 1 is active. Confirm this is intentional, as priority 1 should generally be reserved for emergency or critical control. A critical priority level is active. Review the writable priority array and confirm the command source. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements. A priority command appears active outside configured business hours. Review whether the point is being held on manually.
WRITABLE_POINT_FOUND STATUS_LIKE_POINT POINT_OVERRIDDEN STATUS_OUTPUT_ACTIVE FAULT_OR_ALARM_ACTIVE PRIORITY_ARRAY_ACTIVE CRITICAL_PRIORITY_ACTIVE PRIORITY_1_ACTIVE CRITICAL_OUT_PRIORITY_SOURCE AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS_PRIORITY_ACTIVE
Priority array and schedule details
Enabled
Fallback -
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1 true {ok}
Priority 2 - {null}
Priority 3 - {null}
Priority 4 - {null}
Priority 5 - {null}
Priority 6 - {null}
Priority 7 - {null}
Priority 8 - {null}
Priority 9 - {null}
Priority 10 - {null}
Priority 11 - {null}
Priority 12 - {null}
Priority 13 - {null}
Priority 14 - {null}
Priority 15 - {null}
Priority 16 - {null}
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/PHEX_02/GUI/Fault_Logic/Low_Temp_Fault

#24 FAULT_OR_ALARM_ACTIVE

GUI_Fault | Drivers/NiagaraNetwork/Site_Y/points/PHEX_03/GUI/Fault_Logic/GUI_Fault
HIGH
Category ALARM_FAULT
Action Alarms / Commissioning
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/PHEX_03/GUI/Fault_Logic
Identity faultlogic
Out true
Out status ok
Out priority 16
Active priorities 1
Highest priority 16
Highest value true
Schedule
Command
Status
Fault / alarm
Recommendation: Fault or alarm point is active. Review the active alarm condition and associated equipment. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements. A priority command appears active outside configured business hours. Review whether the point is being held on manually.
WRITABLE_POINT_FOUND STATUS_LIKE_POINT STATUS_OUTPUT_ACTIVE FAULT_OR_ALARM_ACTIVE PRIORITY_ARRAY_ACTIVE AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS_PRIORITY_ACTIVE
Priority array and schedule details
Enabled
Fallback -
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1 - {null}
Priority 2 - {null}
Priority 3 - {null}
Priority 4 - {null}
Priority 5 - {null}
Priority 6 - {null}
Priority 7 - {null}
Priority 8 - {null}
Priority 9 - {null}
Priority 10 - {null}
Priority 11 - {null}
Priority 12 - {null}
Priority 13 - {null}
Priority 14 - {null}
Priority 15 - {null}
Priority 16 true {ok}
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/PHEX_03/GUI/Fault_Logic/GUI_Fault

#25 FAULT_OR_ALARM_ACTIVE

Low_Temp_Fault | Drivers/NiagaraNetwork/Site_Y/points/PHEX_03/GUI/Fault_Logic/Low_Temp_Fault
HIGH
Category ALARM_FAULT
Action Alarms / Commissioning
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/PHEX_03/GUI/Fault_Logic
Identity faultlogic
Out true
Out status overridden
Out priority 1
Active priorities 1
Highest priority 1
Highest value true
Schedule
Command
Status
Fault / alarm
Recommendation: Fault or alarm point is active. Review the active alarm condition and associated equipment. Point status indicates overridden. Confirm this override is intentional and still required. Output appears driven from a critical priority source. Review the command source and release if not required. Priority 1 is active. Confirm this is intentional, as priority 1 should generally be reserved for emergency or critical control. A critical priority level is active. Review the writable priority array and confirm the command source. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements. A priority command appears active outside configured business hours. Review whether the point is being held on manually.
WRITABLE_POINT_FOUND STATUS_LIKE_POINT POINT_OVERRIDDEN STATUS_OUTPUT_ACTIVE FAULT_OR_ALARM_ACTIVE PRIORITY_ARRAY_ACTIVE CRITICAL_PRIORITY_ACTIVE PRIORITY_1_ACTIVE CRITICAL_OUT_PRIORITY_SOURCE AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS_PRIORITY_ACTIVE
Priority array and schedule details
Enabled
Fallback -
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1 true {ok}
Priority 2 - {null}
Priority 3 - {null}
Priority 4 - {null}
Priority 5 - {null}
Priority 6 - {null}
Priority 7 - {null}
Priority 8 - {null}
Priority 9 - {null}
Priority 10 - {null}
Priority 11 - {null}
Priority 12 - {null}
Priority 13 - {null}
Priority 14 - {null}
Priority 15 - {null}
Priority 16 - {null}
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/PHEX_03/GUI/Fault_Logic/Low_Temp_Fault

#26 CRITICAL_OUT_PRIORITY_SOURCE

Clear_Alarms | Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02/Clear_Alarms
HIGH
Category OVERRIDE
Action Controls / BMS
Confidence LOW
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02
Identity chiller02
Out false
Out status ok
Out priority 2
Active priorities 0
Highest priority 0
Highest value
Schedule
Command
Status
Fault / alarm
Recommendation: Output appears driven from a critical priority source. Review the command source and release if not required.
STATUS_LIKE_POINT STATUS_OUTPUT_INACTIVE CRITICAL_OUT_PRIORITY_SOURCE
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02/Clear_Alarms

#27 COMMAND_ACTIVE_SCHEDULE_OFF

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01/Fan_Enable
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01
Identity fcu01
Out true
Out status ok
Out priority 15
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ 15
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements.
COMMAND_LIKE_POINT COMMAND_OUTPUT_ACTIVE AFTER_HOURS_OUTPUT_ACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01/Fan_Enable

#28 COMMAND_ACTIVE_SCHEDULE_OFF

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01/Fan_Status
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01
Identity fcu01
Out true
Out status unackedAlarm
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ 15
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01/Fan_Status

#29 COMMAND_ACTIVE_SCHEDULE_OFF

OCC$2dSCHEDULE | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01/OCC$2dSCHEDULE
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01
Identity fcu01
Out 0
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ 15
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. This is a schedule output/pass-through point, not the actual Niagara schedule component.
SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE_OUTPUT_POINT_INACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01/OCC$2dSCHEDULE

#30 COMMAND_ACTIVE_SCHEDULE_OFF

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05/Fan_Enable
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05
Identity fcu05
Out true
Out status ok
Out priority def
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements.
COMMAND_LIKE_POINT COMMAND_OUTPUT_ACTIVE AFTER_HOURS_OUTPUT_ACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05/Fan_Enable

#31 COMMAND_ACTIVE_SCHEDULE_OFF

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05/Fan_Status
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05
Identity fcu05
Out true
Out status unackedAlarm
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05/Fan_Status

#32 COMMAND_ACTIVE_SCHEDULE_OFF

OCC$2dSCHEDULE | Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05/OCC$2dSCHEDULE
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05
Identity fcu05
Out 0
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. This is a schedule output/pass-through point, not the actual Niagara schedule component.
SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE_OUTPUT_POINT_INACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05/OCC$2dSCHEDULE

#33 COMMAND_ACTIVE_SCHEDULE_OFF

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08/Fan_Enable
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08
Identity fcu08
Out true
Out status ok
Out priority def
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements.
COMMAND_LIKE_POINT COMMAND_OUTPUT_ACTIVE AFTER_HOURS_OUTPUT_ACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08/Fan_Enable

#34 COMMAND_ACTIVE_SCHEDULE_OFF

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08/Fan_Status
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08
Identity fcu08
Out true
Out status unackedAlarm
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08/Fan_Status

#35 COMMAND_ACTIVE_SCHEDULE_OFF

OCC$2dSCHEDULE | Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08/OCC$2dSCHEDULE
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08
Identity fcu08
Out 0
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ def
Status Fan_Status true {unackedAlarm} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. This is a schedule output/pass-through point, not the actual Niagara schedule component.
SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE_OUTPUT_POINT_INACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08/OCC$2dSCHEDULE

#36 COMMAND_ACTIVE_SCHEDULE_OFF

Fan_Enable | Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09/Fan_Enable
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09
Identity fcu09
Out true
Out status ok
Out priority def
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ def
Status Fan_Status true {ok} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. The Boolean output appears active outside configured business hours. Review schedules, overrides, and after-hours requirements.
COMMAND_LIKE_POINT COMMAND_OUTPUT_ACTIVE AFTER_HOURS_OUTPUT_ACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09/Fan_Enable

#37 COMMAND_ACTIVE_SCHEDULE_OFF

Fan_Status | Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09/Fan_Status
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09
Identity fcu09
Out true
Out status ok
Out priority 16
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ def
Status Fan_Status true {ok} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link.
STATUS_LIKE_POINT STATUS_OUTPUT_ACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09/Fan_Status

#38 COMMAND_ACTIVE_SCHEDULE_OFF

OCC$2dSCHEDULE | Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09/OCC$2dSCHEDULE
MEDIUM
Category SCHEDULE_MISMATCH
Action Controls / Scheduling
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09
Identity fcu09
Out 0
Out status stale
Out priority
Active priorities 0
Highest priority 0
Highest value
Schedule OCC$2dSCHEDULE 0 {stale}
Command Fan_Enable true {ok} @ def
Status Fan_Status true {ok} @ 16
Fault / alarm
Recommendation: Command is active while schedule output is off. Check manual override, after-hours command, or incorrect schedule link. This is a schedule output/pass-through point, not the actual Niagara schedule component.
SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE_OUTPUT_POINT_INACTIVE COMMAND_ACTIVE_SCHEDULE_OFF
COMMAND_ACTIVE_SCHEDULE_OFF
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09/OCC$2dSCHEDULE

#39 POINT_UNACKED_ALARM

Site_Y_Jace | Drivers/NiagaraNetwork/Site_Y_Jace
MEDIUM
Category ALARM_FAULT
Action Alarms / Commissioning
Confidence HIGH
Data quality GOOD
Equipment Drivers/NiagaraNetwork
Identity niagaranetwork
Out false
Out status unackedAlarm
Out priority 16
Active priorities 1
Highest priority 16
Highest value false
Schedule
Command
Status
Fault / alarm
Recommendation: Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
WRITABLE_POINT_FOUND POINT_UNACKED_ALARM PRIORITY_ARRAY_ACTIVE
Priority array and schedule details
Enabled
Fallback -
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1 - {null}
Priority 2 - {null}
Priority 3 - {null}
Priority 4 - {null}
Priority 5 - {null}
Priority 6 - {null}
Priority 7 - {null}
Priority 8 - {null}
Priority 9 - {null}
Priority 10 - {null}
Priority 11 - {null}
Priority 12 - {null}
Priority 13 - {null}
Priority 14 - {null}
Priority 15 - {null}
Priority 16 false {ok}
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y_Jace

#40 POINT_UNACKED_ALARM

Run_Status | Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_01/Run_Status
MEDIUM
Category ALARM_FAULT
Action Alarms / Commissioning
Confidence LOW
Data quality GOOD
Equipment Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_01
Identity ccwp01
Out true
Out status unackedAlarm
Out priority 16 alarmInhibit
Active priorities 0
Highest priority 0
Highest value
Schedule
Command
Status
Fault / alarm
Recommendation: Point has an unacknowledged alarm state. Review and acknowledge if appropriate.
STATUS_LIKE_POINT POINT_UNACKED_ALARM STATUS_OUTPUT_ACTIVE
Priority array and schedule details
Enabled
Fallback
Schedule input
Schedule next time
Schedule next value
Schedule default
Schedule modified
Priority 1
Priority 2
Priority 3
Priority 4
Priority 5
Priority 6
Priority 7
Priority 8
Priority 9
Priority 10
Priority 11
Priority 12
Priority 13
Priority 14
Priority 15
Priority 16
Component ORD local:|station:|slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_01/Run_Status

Schedule / override summary

RankPriorityFindingCategoryActionComponentEquipmentOutPriority SourcePair Assessment
1 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02 false RUNNING_WHILE_DISABLED_NOW
2 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02 true 16 RUNNING_WHILE_DISABLED_NOW
3 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02 false def RUNNING_WHILE_DISABLED_NOW
4 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02 true 16 alarmInhibit RUNNING_WHILE_DISABLED_NOW
5 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02 0 RUNNING_WHILE_DISABLED_NOW
6 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07 false def RUNNING_WHILE_DISABLED_NOW;SCHEDULE_ACTIVE_COMMAND_OFF
7 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07 true 16 alarmInhibit RUNNING_WHILE_DISABLED_NOW;SCHEDULE_ACTIVE_COMMAND_OFF
8 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07 1 10 RUNNING_WHILE_DISABLED_NOW;SCHEDULE_ACTIVE_COMMAND_OFF
9 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/KEF_01 false RUNNING_WHILE_DISABLED_NOW
10 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/KEF_01 true 16 RUNNING_WHILE_DISABLED_NOW
11 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05 false RUNNING_WHILE_DISABLED_NOW
12 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05 true 16 RUNNING_WHILE_DISABLED_NOW
13 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_05 false RUNNING_WHILE_DISABLED_NOW
14 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_05 true 16 RUNNING_WHILE_DISABLED_NOW
15 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_01 false RUNNING_WHILE_DISABLED_NOW
16 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_01 true 16 RUNNING_WHILE_DISABLED_NOW
17 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_02 false RUNNING_WHILE_DISABLED_NOW
18 HIGH RUNNING_WHILE_DISABLED_NOW COMMAND_STATUS_MISMATCH Controls / Mechanical Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/TEF_02 true 16 RUNNING_WHILE_DISABLED_NOW
19 HIGH POINT_DOWN ALARM_FAULT Alarms / Commissioning AlarmSignal
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/LTS_High_Wall_Split false
20 HIGH FAULT_OR_ALARM_ACTIVE ALARM_FAULT Alarms / Commissioning GUI_Fault
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/PHEX_01/GUI/Fault_Logic true 16
21 HIGH FAULT_OR_ALARM_ACTIVE ALARM_FAULT Alarms / Commissioning Low_Temp_Fault
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/PHEX_01/GUI/Fault_Logic true 1
22 HIGH FAULT_OR_ALARM_ACTIVE ALARM_FAULT Alarms / Commissioning GUI_Fault
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/PHEX_02/GUI/Fault_Logic true 16
23 HIGH FAULT_OR_ALARM_ACTIVE ALARM_FAULT Alarms / Commissioning Low_Temp_Fault
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/PHEX_02/GUI/Fault_Logic true 1
24 HIGH FAULT_OR_ALARM_ACTIVE ALARM_FAULT Alarms / Commissioning GUI_Fault
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/PHEX_03/GUI/Fault_Logic true 16
25 HIGH FAULT_OR_ALARM_ACTIVE ALARM_FAULT Alarms / Commissioning Low_Temp_Fault
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/PHEX_03/GUI/Fault_Logic true 1
26 HIGH CRITICAL_OUT_PRIORITY_SOURCE OVERRIDE Controls / BMS Clear_Alarms
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 false 2
27 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 true 15 COMMAND_ACTIVE_SCHEDULE_OFF
28 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 true 16 COMMAND_ACTIVE_SCHEDULE_OFF
29 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 0 COMMAND_ACTIVE_SCHEDULE_OFF
30 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05 true def COMMAND_ACTIVE_SCHEDULE_OFF
31 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05 true 16 COMMAND_ACTIVE_SCHEDULE_OFF
32 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05 0 COMMAND_ACTIVE_SCHEDULE_OFF
33 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08 true def COMMAND_ACTIVE_SCHEDULE_OFF
34 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08 true 16 COMMAND_ACTIVE_SCHEDULE_OFF
35 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08 0 COMMAND_ACTIVE_SCHEDULE_OFF
36 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09 true def COMMAND_ACTIVE_SCHEDULE_OFF
37 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09 true 16 COMMAND_ACTIVE_SCHEDULE_OFF
38 MEDIUM COMMAND_ACTIVE_SCHEDULE_OFF SCHEDULE_MISMATCH Controls / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09 0 COMMAND_ACTIVE_SCHEDULE_OFF
39 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Site_Y_Jace
control:BooleanWritable
Drivers/NiagaraNetwork false 16
40 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_01 true 16 alarmInhibit
41 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false 16
42 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false 16 alarmInhibit
43 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning At_Least_1_Alarm_Active
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 false
44 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 true 16 alarmInhibit
45 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_01 false 16 alarmInhibit
46 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler true 16
47 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04 false 16 alarmInhibit
48 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/Boiler_02 true 10
49 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_01 true 16
50 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_02 true 16
51 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_03 false 16
52 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_03 true 16
53 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Lift_1_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Lifts false
54 MEDIUM POINT_UNACKED_ALARM ALARM_FAULT Alarms / Commissioning Lift_2_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Lifts false
55 MEDIUM AFTER_HOURS_PRIORITY_ACTIVE AFTER_HOURS Operations / Energy Review Ch1_EnteringWater
control:NumericWritable
Drivers/NiagaraNetwork/Site_Y/points/CHW_System 26.90 10
56 MEDIUM AFTER_HOURS_PRIORITY_ACTIVE AFTER_HOURS Operations / Energy Review Ch1_LeavingWater
control:NumericWritable
Drivers/NiagaraNetwork/Site_Y/points/CHW_System 13.80 10
57 MEDIUM AFTER_HOURS_PRIORITY_ACTIVE AFTER_HOURS Operations / Energy Review Ch2_EnteringWater
control:NumericWritable
Drivers/NiagaraNetwork/Site_Y/points/CHW_System 11.20 10
58 MEDIUM AFTER_HOURS_PRIORITY_ACTIVE AFTER_HOURS Operations / Energy Review Ch2_LeavingWater
control:NumericWritable
Drivers/NiagaraNetwork/Site_Y/points/CHW_System 7.60 10
59 MEDIUM AFTER_HOURS_PRIORITY_ACTIVE AFTER_HOURS Operations / Energy Review EnteringWaterTemp
control:NumericWritable
Drivers/NiagaraNetwork/Site_Y/points/CHW_System 11.20 10
60 MEDIUM AFTER_HOURS_PRIORITY_ACTIVE AFTER_HOURS Operations / Energy Review LeavingWaterTemp
control:NumericWritable
Drivers/NiagaraNetwork/Site_Y/points/CHW_System 7.60 10
61 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_01 true 14
62 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 true 16
63 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler true 16
64 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/Boiler_01 true 10
65 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/Boiler_02 true 10
66 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_01 true 10
67 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_02 true 10
68 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_03 true 10
69 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_01 true 16
70 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_02 true 16
71 MEDIUM AFTER_HOURS_OUTPUT_ACTIVE AFTER_HOURS Operations / Energy Review Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_03 true 16
72 MEDIUM AFTER_HOURS_SCHEDULE_ACTIVE AFTER_HOURS Operations / Energy Review AHU_AH_Schedule
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules true
73 MEDIUM AFTER_HOURS_SCHEDULE_ACTIVE AFTER_HOURS Operations / Energy Review AHU_Schedule
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules true
74 MEDIUM AFTER_HOURS_SCHEDULE_ACTIVE AFTER_HOURS Operations / Energy Review Carpark_Schedule
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules true
75 MEDIUM AFTER_HOURS_SCHEDULE_ACTIVE AFTER_HOURS Operations / Energy Review Gym_Reception_FirstAid
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules true
76 MEDIUM AFTER_HOURS_SCHEDULE_ACTIVE AFTER_HOURS Operations / Energy Review Pool_Schedule
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules true
77 MEDIUM AFTER_HOURS_SCHEDULE_ACTIVE AFTER_HOURS Operations / Energy Review Pool_Stores
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules true
78 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 false
79 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02 false
80 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03 0
81 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03 false
82 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04 0
83 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04 false
84 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05 false
85 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06 0
86 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06 false
87 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_14 0
88 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_14 false
89 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08 false
90 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09 false
91 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10 0
92 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10 false
93 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11 0
94 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11 false
95 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_12 0
96 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_12 false
97 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13 0
98 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13 false
99 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15 0
100 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15 false
101 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling OCC$2dSCHEDULE
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16 0
102 LOW SCHEDULE_OUTPUT_POINT_FOUND SCHEDULE Operations / Scheduling Occupancy
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16 false
103 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling FirstFloor_Offices
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
104 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling FirstFloorMultiRoom_Lobby_Toilets
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
105 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling Ground_and_Level_1
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
106 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling Kiosk
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
107 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling Level_1_Multi_new
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
108 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling LTS_Office
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
109 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling LTS_Office$2dOld$2dLeave
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
110 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling Pool_Hall_Amenities
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
111 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling Pool_Morning_Warm_Up
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
112 LOW BOOLEAN_SCHEDULE_COMPONENT_FOUND SCHEDULE Operations / Scheduling PoolHall_FreshAir
schedule:BooleanSchedule
Drivers/NiagaraNetwork/Site_Y/points/Schedules false
113 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS StatusDemux
kitControl:StatusDemux
Drivers/NiagaraNetwork
114 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/BTEF_01 false
115 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/BTEF_01 false
116 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/BTEF_01 false
117 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/BTEF_01 false
118 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/CPEF_01 false
119 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable_SP_Co
control:NumericPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/CPEF_01 0.00
120 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/CPEF_01 false
121 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/CPEF_01 false
122 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/CPEF_02 false
123 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable_SP_Co
control:NumericPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/CPEF_02 0.00
124 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/CPEF_02 false
125 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/CPEF_02 false
126 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/EF_01 false
127 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/EF_01 false
128 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/EF_07 false
129 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/EF_07 false
130 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/PPSF_01 false
131 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/PPSF_01 false
132 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/PPSF_01 false
133 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/PPSF_01 false
134 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/SREF_01 false
135 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Basement_Fans/SREF_01 false
136 LOW WRITABLE_POINT_FOUND POINT_STATE Controls / BMS Chwp_Running
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/CHW_System - def
137 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_01 false
138 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_01 false
139 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_01 false
140 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_02 false
141 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_02 false 9
142 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_02 false
143 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_02 false
144 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CCWP_02 false 16 alarmInhibit
145 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Alarm_Summary
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
146 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Circuit_1_High_Pressure_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
147 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Circuit_1_Low_Pressure_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
148 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Circuit_2_High_Pressure_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
149 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Circuit_2_Low_Pressure_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
150 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Compressor_1_Circuit_1_CB_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
151 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Compressor_1_Circuit_2_CB_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
152 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Compressor_2_Circuit_1_CB_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
153 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Compressor_2_Circuit_2_CB_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
154 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false 16
155 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS On_Off_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01 false
156 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Compressor_1_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 false
157 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Compressor_2_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 false
158 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 false 16
159 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS General_Alarm
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02 false def
160 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_01 false
161 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_01 false
162 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_01 false
163 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_01 false 16
164 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02 false
165 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02 false
166 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02 false
167 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_01 false
168 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_010 false
169 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_011 false
170 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_012 false
171 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_013 false
172 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_014 false
173 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_015 false
174 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_016 false
175 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_02 false
176 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_03 false
177 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_04 false
178 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_05 false
179 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_06 false
180 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_07 false
181 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_08 false
182 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CHW_System/FCU_Valves/FCU_09 false
183 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CoGen_Plant false 10
184 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Failure_To_Start
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/CoGen_Plant false
185 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Logic
niagaraDriver:NiagaraPointFolder
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler
186 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS PHEX_02_Override_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler false
187 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS PHEX_03_Override_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler false
188 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Spray_Pump_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler false
189 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler/CCFC_01 false
190 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler/CCFC_01 false
191 LOW WRITABLE_POINT_FOUND POINT_STATE Controls / BMS GUI_Fault
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler/Fault_Logic/Fluid_Cooler false 16
192 LOW WRITABLE_POINT_FOUND POINT_STATE Controls / BMS High_Temp_Fault
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler/Fault_Logic/Fluid_Cooler - def
193 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS FCU_02_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 false
194 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS FCU_03_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 false
195 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS FCU_04_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 false
196 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS FCU_05_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01 false
197 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03 false
198 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03 false
199 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04 false def
200 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06 false
201 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06 false
202 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_14 false
203 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_14 false
204 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/OAF_01 false
205 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/OAF_01 false
206 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS CH_1_Fault
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HighWallSplit false
207 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS CH_2_Fault
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HighWallSplit false
208 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HighWallSplit false
209 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/Boiler_01 false
210 LOW STATUS_OUTPUT_ACTIVE POINT_STATE Controls / BMS Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/Boiler_01 true 10
211 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/Boiler_02 false
212 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Enable
niagaraDriver:NiagaraPointFolder
Drivers/NiagaraNetwork/Site_Y/points/HW_System/CCWP
213 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS ByPass_Enable_SP
control:NumericPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/CCWP/Control 0.00
214 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_01 false
215 LOW STATUS_OUTPUT_ACTIVE POINT_STATE Controls / BMS Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_01 true
216 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_02 false
217 LOW STATUS_OUTPUT_ACTIVE POINT_STATE Controls / BMS Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_02 true
218 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_03 false
219 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_03 false
220 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_03 false
221 LOW STATUS_OUTPUT_ACTIVE POINT_STATE Controls / BMS Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_03 true
222 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_04 false
223 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_04 false 10
224 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_04 false
225 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_04 false
226 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_04 false
227 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_01 false
228 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_01 false
229 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_01 false 16
230 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_02 false
231 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_02 false
232 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_02 false 16
233 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS ALARM$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_03 false
234 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS FAULT$20ACT
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_03 false
235 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/EF_06 false
236 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/EF_06 false
237 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10 false
238 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10 false
239 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11 false
240 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11 false
241 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_12 false
242 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_12 false
243 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13 false
244 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13 false
245 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15 false
246 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15 false
247 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16 false
248 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16 false
249 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/TEF_03 false
250 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/TEF_03 false
251 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/TEF_04 false
252 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/TEF_04 false
253 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Device$20Object$2dsystemStatus
control:EnumPoint
Drivers/NiagaraNetwork/Site_Y/points/LTS_High_Wall_Split 0
254 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Logic
baja:Folder
Drivers/NiagaraNetwork/Site_Y/points/PHEX_01
255 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Logic
baja:Folder
Drivers/NiagaraNetwork/Site_Y/points/PHEX_02
256 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fault_Logic
baja:Folder
Drivers/NiagaraNetwork/Site_Y/points/PHEX_03
257 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS EnableFreshAir
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05/FreshAirDamper false
258 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS Fan_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_04 false
259 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS Fan_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/EF_04 false
260 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS EAF_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/ERV_01 false
261 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS EAF_Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/ERV_01 false
262 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS EAF_Status
control:NumericPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/ERV_01 0.00
263 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS OA_to_RA_Filter_Status
control:NumericPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/ERV_01 0.00
264 LOW COMMAND_LIKE_POINT POINT_STATE Controls / BMS OAF_Enable
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/ERV_01 false
265 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS OAF_Run_Status
control:BooleanPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/ERV_01 false
266 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS OAF_Status
control:NumericPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/ERV_01 0.00
267 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS RA_EXH_Filter_Status
control:NumericPoint
Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/ERV_01 0.00
268 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS BooleanChangeOfStateAlarmExt
alarm:AlarmSourceExt
Drivers/NiagaraNetwork/Site_Y_Jace
269 LOW STATUS_LIKE_POINT POINT_STATE Controls / BMS faultAlgorithm
alarm:FaultAlgorithm
Drivers/NiagaraNetwork/Site_Y_Jace/BooleanChangeOfStateAlarmExt
270 LOW WRITABLE_POINT_FOUND GENERAL Review BooleanWritable
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points - def
271 LOW WRITABLE_POINT_FOUND GENERAL Review Chwp_1
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/CHW_System - def
272 LOW WRITABLE_POINT_FOUND GENERAL Review Chwp_2
control:BooleanWritable
Drivers/NiagaraNetwork/Site_Y/points/CHW_System - def

Run counters

Components scanned 5989
Writable-like found 19
Schedule components 16
Schedule output points 31
Helper skipped 3242
Equipment groups 62
Pair findings 13
Rows written 272
Summary rows 77
Mismatches 30
Alarm / fault 23
Data quality 0

Run configuration

Business start 7.0
Business end 18.0
Weekends business true
High priority threshold 8.0
Critical threshold 2.0
Scan writable true
Scan schedules true
Scan commands true
Scan status pairs true