Stage 4

Energy Audit

A readable summary of meter load, kWh and kW agreement, after-hours load, base load, power factor, phase imbalance, history coverage, and data quality.

StageBUILDING_INTELLIGENCE_STAGE_4_ENERGY_AUDIT
Versionstage4.energy.0.2
Export time2026-06-25T21:12:35+1000
Sample window2026-06-18T21:12:34+1000 to 2026-06-25T21:12:34+1000
Meters analysed11
HIGH
9

Meters requiring immediate review.

MEDIUM
0

Meters with findings worth reviewing.

AVG SCORE
16.36

Average energy summary score. Higher is better.

DATA QUALITY
11

Meters with stale, partial, missing, or questionable data.

PERIOD KWH
4262.2

Total kWh measured from available counters.

EST. KWH
158030.32

Total kWh estimated from kW samples.

High-priority energy findings detected

Review the top action cards first. These usually indicate kW/kWh disagreement, extreme kW values, no usable data, current imbalance, or other material meter issues.

How to read this report

Energy score starts at 100 and is reduced by priority, data quality issues, high after-hours load, high base load, poor power factor, phase imbalance, extreme kW values, and kW/kWh disagreement.

Period kWh comes from the cumulative kWh counter. Estimated kWh is integrated from kW samples. A large difference usually points to scaling, units, reset, rollover, or mapping problems.

Top action findings

#1 KW_KWH_DISAGREE

CoGen | Energy_Meters/CoGen
HIGH
Energy score 0
Audit status ANALYSED
Data quality PARTIAL
Confidence MEDIUM
Period kWh 0.0
Estimated kWh from kW 590.87
kW/kWh difference 100.0%
Average kW 3.52
Peak kW 6.5
Peak timestamp 2026-06-19T23:12:34+1000
Base load kW 0.0
After-hours avg kW 3.28
After-hours ratio 0.93
Average PF 0.0
Min PF 0.0
Low PF hours 168.0
Voltage imbalance max 0.98%
Current imbalance max 175.46%
Buckets analysed 672 / 672
Recommendation: kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
KWH_DECREASED HIGH_AFTER_HOURS_LOAD LOW_POWER_FACTOR CURRENT_IMBALANCE KW_KWH_DISAGREE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED POWER_FACTOR_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED CURRENT_A_CARRY_FORWARD_USED CURRENT_B_CARRY_FORWARD_USED CURRENT_C_CARRY_FORWARD_USED CURRENT_IMBALANCE_SKIPPED_LOW_LOAD KWH_COUNTER_DECREASED KW_KWH_DISAGREE
Mapped histories
kW /Site_Y/CoGeneration_Board_KW
kWh /Site_Y/CoGeneration_Board_KWH
Power factor /Site_Y/CoGeneration_Board_PF
Voltage A /Site_Y/CoGeneration_Board_V_A_N
Voltage B /Site_Y/CoGeneration_Board_V_B_N
Voltage C /Site_Y/CoGeneration_Board_V_C_N
Current A /Site_Y/CoGeneration_Board_I_A
Current B /Site_Y/CoGeneration_Board_I_B
Current C /Site_Y/CoGeneration_Board_I_C

#2 KW_KWH_DISAGREE

DB_01 | Energy_Meters/DB_01
HIGH
Energy score 0
Audit status ANALYSED
Data quality PARTIAL
Confidence MEDIUM
Period kWh 906.8
Estimated kWh from kW 38979.25
kW/kWh difference 97.67%
Average kW 232.02
Peak kW 236.3
Peak timestamp 2026-06-24T11:57:34+1000
Base load kW 225.9
After-hours avg kW 231.74
After-hours ratio 1.0
Average PF 0.0
Min PF 0.0
Low PF hours 0.0
Voltage imbalance max 1.7%
Current imbalance max 0.0%
Buckets analysed 672 / 672
Recommendation: kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption.
HIGH_AFTER_HOURS_LOAD HIGH_BASE_LOAD KW_KWH_DISAGREE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED KW_KWH_DISAGREE
Mapped histories
kW /Site_Y/DB_1_Power_V_A_N
kWh /Site_Y/DB_1_Lighting_KWH
Power factor
Voltage A /Site_Y/DB_1_Lighting_V_A_N
Voltage B /Site_Y/DB_1_Lighting_V_B_N
Voltage C /Site_Y/DB_1_Lighting_V_C_N
Current A
Current B
Current C

#3 KW_KWH_DISAGREE

DB_CP_01 | Energy_Meters/DB_CP_01
HIGH
Energy score 0
Audit status ANALYSED
Data quality PARTIAL
Confidence MEDIUM
Period kWh 374.4
Estimated kWh from kW 39223.18
kW/kWh difference 99.05%
Average kW 233.47
Peak kW 236.0
Peak timestamp 2026-06-20T21:42:34+1000
Base load kW 229.7
After-hours avg kW 233.43
After-hours ratio 1.0
Average PF 0.0
Min PF 0.0
Low PF hours 0.0
Voltage imbalance max 1.04%
Current imbalance max 0.0%
Buckets analysed 672 / 672
Recommendation: kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption.
HIGH_AFTER_HOURS_LOAD HIGH_BASE_LOAD KW_KWH_DISAGREE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED KW_KWH_DISAGREE
Mapped histories
kW /Site_Y/DB_CP1_Power_V_A_N
kWh /Site_Y/DB_CP1_Lighting_KWH
Power factor
Voltage A /Site_Y/DB_CP1_Lighting_V_A_N
Voltage B /Site_Y/DB_CP1_Lighting_V_B_N
Voltage C /Site_Y/DB_CP1_Lighting_V_C_N
Current A
Current B
Current C

#4 KW_KWH_DISAGREE

DB_CP_02 | Energy_Meters/DB_CP_02
HIGH
Energy score 0
Audit status ANALYSED
Data quality PARTIAL
Confidence MEDIUM
Period kWh 0.0
Estimated kWh from kW 38935.87
kW/kWh difference 100.0%
Average kW 231.76
Peak kW 234.7
Peak timestamp 2026-06-21T21:57:34+1000
Base load kW 227.5
After-hours avg kW 231.84
After-hours ratio 1.0
Average PF 0.0
Min PF 0.0
Low PF hours 0.0
Voltage imbalance max 1.27%
Current imbalance max 0.0%
Buckets analysed 672 / 672
Recommendation: kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption.
KWH_DECREASED HIGH_AFTER_HOURS_LOAD HIGH_BASE_LOAD KW_KWH_DISAGREE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED KWH_COUNTER_DECREASED KW_KWH_DISAGREE
Mapped histories
kW /Site_Y/DB_CP2_Power_V_A_N
kWh /Site_Y/DB_CP2_Lighting_KWH
Power factor
Voltage A /Site_Y/DB_CP2_Lighting_V_A_N
Voltage B /Site_Y/DB_CP2_Lighting_V_B_N
Voltage C /Site_Y/DB_CP2_Lighting_V_C_N
Current A
Current B
Current C

#5 KW_KWH_DISAGREE

DB_Cafe | Energy_Meters/DB_Cafe
HIGH
Energy score 0
Audit status ANALYSED
Data quality PARTIAL
Confidence MEDIUM
Period kWh 6.9
Estimated kWh from kW 39232.85
kW/kWh difference 99.98%
Average kW 233.53
Peak kW 236.1
Peak timestamp 2026-06-24T21:42:34+1000
Base load kW 229.4
After-hours avg kW 233.51
After-hours ratio 1.0
Average PF 0.0
Min PF 0.0
Low PF hours 0.0
Voltage imbalance max 1.08%
Current imbalance max 0.0%
Buckets analysed 672 / 672
Recommendation: kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption.
HIGH_AFTER_HOURS_LOAD HIGH_BASE_LOAD KW_KWH_DISAGREE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED KW_KWH_DISAGREE
Mapped histories
kW /Site_Y/DB_Cafe_Power_V_A_N
kWh /Site_Y/DB_Cafe_Lighting_KWH
Power factor
Voltage A /Site_Y/DB_Cafe_Lighting_V_A_N
Voltage B /Site_Y/DB_Cafe_Lighting_V_B_N
Voltage C /Site_Y/DB_Cafe_Lighting_V_C_N
Current A
Current B
Current C

#6 KW_KWH_DISAGREE

DB_Lift_A | Energy_Meters/DB_Lift_A
HIGH
Energy score 0
Audit status ANALYSED
Data quality PARTIAL
Confidence MEDIUM
Period kWh 77.9
Estimated kWh from kW 54.07
kW/kWh difference 30.58%
Average kW 0.32
Peak kW 5.8
Peak timestamp 2026-06-22T14:42:34+1000
Base load kW 0.1
After-hours avg kW 0.27
After-hours ratio 0.84
Average PF 0.0
Min PF 0.0
Low PF hours 168.0
Voltage imbalance max 0.91%
Current imbalance max 95.52%
Buckets analysed 672 / 672
Recommendation: kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
CURRENT_IMBALANCE KW_KWH_DISAGREE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED POWER_FACTOR_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED CURRENT_A_CARRY_FORWARD_USED CURRENT_B_CARRY_FORWARD_USED CURRENT_C_CARRY_FORWARD_USED CURRENT_IMBALANCE_SKIPPED_LOW_LOAD KW_KWH_DISAGREE
Mapped histories
kW /Site_Y/Lift_1_KW
kWh /Site_Y/Lift_1_KWH
Power factor /Site_Y/Lift_1_PF
Voltage A /Site_Y/Lift_1_V_A_N
Voltage B /Site_Y/Lift_1_V_B_N
Voltage C /Site_Y/Lift_1_V_C_N
Current A /Site_Y/Lift_1_I_A
Current B /Site_Y/Lift_1_I_B
Current C /Site_Y/Lift_1_I_C

#7 KW_KWH_DISAGREE

MSSB_01 | Energy_Meters/MSSB_01
HIGH
Energy score 0
Audit status ANALYSED
Data quality PARTIAL
Confidence MEDIUM
Period kWh 940.7
Estimated kWh from kW 573.88
kW/kWh difference 38.99%
Average kW 3.42
Peak kW 6.5
Peak timestamp 2026-06-19T09:12:34+1000
Base load kW 0.0
After-hours avg kW 3.41
After-hours ratio 1.0
Average PF 0.0
Min PF 0.0
Low PF hours 168.0
Voltage imbalance max 1.08%
Current imbalance max 181.03%
Buckets analysed 672 / 672
Recommendation: kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
HIGH_AFTER_HOURS_LOAD LOW_POWER_FACTOR CURRENT_IMBALANCE KW_KWH_DISAGREE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED POWER_FACTOR_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED CURRENT_A_CARRY_FORWARD_USED CURRENT_B_CARRY_FORWARD_USED CURRENT_C_CARRY_FORWARD_USED CURRENT_IMBALANCE_SKIPPED_LOW_LOAD KW_KWH_DISAGREE
Mapped histories
kW /Site_Y/MSSB_01_KW
kWh /Site_Y/MSSB_01_KWH
Power factor /Site_Y/MSSB_01_PF
Voltage A /Site_Y/MSSB_01_V_A_N
Voltage B /Site_Y/MSSB_01_V_B_N
Voltage C /Site_Y/MSSB_01_V_C_N
Current A /Site_Y/MSSB_01_I_A
Current B /Site_Y/MSSB_01_I_B
Current C /Site_Y/MSSB_01_I_C

#8 KW_KWH_DISAGREE

MSSB_02 | Energy_Meters/MSSB_02
HIGH
Energy score 0
Audit status ANALYSED
Data quality PARTIAL
Confidence MEDIUM
Period kWh 1861.2
Estimated kWh from kW 368.35
kW/kWh difference 80.21%
Average kW 2.19
Peak kW 6.6
Peak timestamp 2026-06-20T15:57:34+1000
Base load kW 0.0
After-hours avg kW 2.59
After-hours ratio 1.18
Average PF 0.0
Min PF 0.0
Low PF hours 168.0
Voltage imbalance max 1.02%
Current imbalance max 11.22%
Buckets analysed 672 / 672
Recommendation: kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
HIGH_AFTER_HOURS_LOAD LOW_POWER_FACTOR KW_KWH_DISAGREE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED POWER_FACTOR_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED CURRENT_A_CARRY_FORWARD_USED CURRENT_B_CARRY_FORWARD_USED CURRENT_C_CARRY_FORWARD_USED CURRENT_IMBALANCE_SKIPPED_LOW_LOAD KW_KWH_DISAGREE
Mapped histories
kW /Site_Y/MSSB_02_KW
kWh /Site_Y/MSSB_02_KWH
Power factor /Site_Y/MSSB_02_PF
Voltage A /Site_Y/MSSB_02_V_A_N
Voltage B /Site_Y/MSSB_02_V_B_N
Voltage C /Site_Y/MSSB_02_V_C_N
Current A /Site_Y/MSSB_02_I_A
Current B /Site_Y/MSSB_02_I_B
Current C /Site_Y/MSSB_02_I_C

#9 KWH_ONLY_USAGE

MSSB_03 | Energy_Meters/MSSB_03
HIGH
Energy score 0
Audit status ANALYSED
Data quality PARTIAL
Confidence MEDIUM
Period kWh 5.8
Estimated kWh from kW 0.0
kW/kWh difference 100.0%
Average kW 0.0
Peak kW 0.0
Peak timestamp 2026-06-18T21:12:34+1000
Base load kW 0.0
After-hours avg kW 0.0
After-hours ratio 0.0
Average PF 0.0
Min PF 0.0
Low PF hours 168.0
Voltage imbalance max 0.8%
Current imbalance max 0.0%
Buckets analysed 672 / 672
Recommendation: kWh counter increased while kW-derived usage was zero or unavailable. Check whether true power is disabled, scaled incorrectly, mapped to the wrong point, or not recording useful values. kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
KWH_ONLY_USAGE KW_KWH_DISAGREE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED POWER_FACTOR_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED CURRENT_A_CARRY_FORWARD_USED CURRENT_B_CARRY_FORWARD_USED CURRENT_C_CARRY_FORWARD_USED CURRENT_IMBALANCE_SKIPPED_LOW_LOAD KW_ZERO_WHILE_KWH_INCREASED KW_KWH_DISAGREE
Mapped histories
kW /Site_Y/MSSB_03_KW
kWh /Site_Y/MSSB_03_KWH
Power factor /Site_Y/MSSB_03_PF
Voltage A /Site_Y/MSSB_03_V_A_N
Voltage B /Site_Y/MSSB_03_V_B_N
Voltage C /Site_Y/MSSB_03_V_C_N
Current A /Site_Y/MSSB_03_I_A
Current B /Site_Y/MSSB_03_I_B
Current C /Site_Y/MSSB_03_I_C

#10 NO_MAJOR_ENERGY_FINDING

Chiller_01 | CHW_System/Chiller_01
LOW
Energy score 90
Audit status ANALYSED
Data quality GOOD_WITH_CARRY_FORWARD
Confidence HIGH
Period kWh 0.0
Estimated kWh from kW 0.0
kW/kWh difference 0.0%
Average kW 0.0
Peak kW 0.0
Peak timestamp 2026-06-18T21:12:34+1000
Base load kW 0.0
After-hours avg kW 0.0
After-hours ratio 0.0
Average PF 0.0
Min PF 0.0
Low PF hours 0.0
Voltage imbalance max 0.0%
Current imbalance max 0.0%
Buckets analysed 672 / 672
Recommendation: Energy meter histories analysed. No major energy issue detected from available data.
NONE
KW_CARRY_FORWARD_USED
Mapped histories
kW /Site_Y/Chiller_1_Actual_Power_Capacity
kWh
Power factor
Voltage A
Voltage B
Voltage C
Current A
Current B
Current C

#11 NO_MAJOR_ENERGY_FINDING

DB_Lift_B | Energy_Meters/DB_Lift_B
LOW
Energy score 90
Audit status ANALYSED
Data quality GOOD_WITH_CARRY_FORWARD
Confidence HIGH
Period kWh 88.5
Estimated kWh from kW 72.0
kW/kWh difference 18.64%
Average kW 0.43
Peak kW 6.2
Peak timestamp 2026-06-20T10:42:34+1000
Base load kW 0.0
After-hours avg kW 0.32
After-hours ratio 0.74
Average PF 0.0
Min PF 0.0
Low PF hours 168.0
Voltage imbalance max 0.77%
Current imbalance max 18.13%
Buckets analysed 672 / 672
Recommendation: Some current imbalance checks were skipped because average load was below the configured minimum current threshold.
NONE
KW_CARRY_FORWARD_USED KWH_CARRY_FORWARD_USED POWER_FACTOR_CARRY_FORWARD_USED VOLTAGE_A_CARRY_FORWARD_USED VOLTAGE_B_CARRY_FORWARD_USED VOLTAGE_C_CARRY_FORWARD_USED CURRENT_A_CARRY_FORWARD_USED CURRENT_B_CARRY_FORWARD_USED CURRENT_C_CARRY_FORWARD_USED CURRENT_IMBALANCE_SKIPPED_LOW_LOAD
Mapped histories
kW /Site_Y/Lift_2_KW
kWh /Site_Y/Lift_2_KWH
Power factor /Site_Y/Lift_2_PF
Voltage A /Site_Y/Lift_2_V_A_N
Voltage B /Site_Y/Lift_2_V_B_N
Voltage C /Site_Y/Lift_2_V_C_N
Current A /Site_Y/Lift_2_I_A
Current B /Site_Y/Lift_2_I_B
Current C /Site_Y/Lift_2_I_C

Energy meter summary

RankPriorityScoreMeterStatusPrimary findingData qualityConfidencePeriod kWhAvg kWMax kWAfter-hours ratioPF avgV imb maxI imb max
1 HIGH 0 CoGen ANALYSED KW_KWH_DISAGREE PARTIAL MEDIUM 0.0 3.52 6.5 0.93 0.0 0.98 175.46
2 HIGH 0 DB_01 ANALYSED KW_KWH_DISAGREE PARTIAL MEDIUM 906.8 232.02 236.3 1.0 0.0 1.7 0.0
3 HIGH 0 DB_CP_01 ANALYSED KW_KWH_DISAGREE PARTIAL MEDIUM 374.4 233.47 236.0 1.0 0.0 1.04 0.0
4 HIGH 0 DB_CP_02 ANALYSED KW_KWH_DISAGREE PARTIAL MEDIUM 0.0 231.76 234.7 1.0 0.0 1.27 0.0
5 HIGH 0 DB_Cafe ANALYSED KW_KWH_DISAGREE PARTIAL MEDIUM 6.9 233.53 236.1 1.0 0.0 1.08 0.0
6 HIGH 0 DB_Lift_A ANALYSED KW_KWH_DISAGREE PARTIAL MEDIUM 77.9 0.32 5.8 0.84 0.0 0.91 95.52
7 HIGH 0 MSSB_01 ANALYSED KW_KWH_DISAGREE PARTIAL MEDIUM 940.7 3.42 6.5 1.0 0.0 1.08 181.03
8 HIGH 0 MSSB_02 ANALYSED KW_KWH_DISAGREE PARTIAL MEDIUM 1861.2 2.19 6.6 1.18 0.0 1.02 11.22
9 HIGH 0 MSSB_03 ANALYSED KWH_ONLY_USAGE PARTIAL MEDIUM 5.8 0.0 0.0 0.0 0.0 0.8 0.0
10 LOW 90 Chiller_01 ANALYSED NO_MAJOR_ENERGY_FINDING GOOD_WITH_CARRY_FORWARD HIGH 0.0 0.0 0.0 0.0 0.0 0.0 0.0
11 LOW 90 DB_Lift_B ANALYSED NO_MAJOR_ENERGY_FINDING GOOD_WITH_CARRY_FORWARD HIGH 88.5 0.43 6.2 0.74 0.0 0.77 18.13

Run configuration

Lookback days 7.0
Sample interval 15.0 min
Carry-forward true
Max carry-forward 7.0 days
Business hours 7.0 to 18.0
Weekends business false
Low PF threshold 0.9
Voltage imbalance threshold 2.0%
Current imbalance threshold 20.0%
Current min avg amps 5.0
Current min bucket count 12.0
Voltage min avg volts 200.0
Minimum avg kW 0.5
After-hours ratio threshold 0.35
Base-load ratio threshold 0.3
kW/kWh disagreement 30.0%
Extreme kW threshold 100000.0
No usable data 0
Total after-hours avg kW 940.39