Building Health Action Report

BUILDING_INTELLIGENCE_STAGE_10_MASTER_REPORT | stage10.masterReport.0.1 | 2026-06-25T21:12:17+1000

Executive Summary

0.0
Building health score
56
Total findings
33
High priority
19
Medium priority
40
Equipment with findings
27
Runtime findings
18
Comfort/control findings
11
Energy findings
0
Data quality findings

Input Coverage

Source StageFileStatusRowsMessage
STAGE_2_RUNTIME runtime_audit.csv OK 27 Runtime audit rows read.
STAGE_3_THERMAL thermal_audit.csv OK 18 Thermal audit rows read.
STAGE_4_ENERGY energy_audit.csv OK 11 Energy audit rows read.

Top Action Items

RankPriorityScoreCategoryEquipmentFindingEvidenceRecommended ActionConfidence
1 HIGH 88.0 COMFORT_CONTROL FCU_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01
COOLING_VALVE_HUNTING
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 30; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 1.25; Zone below setpoint hours: 0.5; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.75; Heating valve open supply not warm hours: 1.75; Cooling valve movement: 2921.0; Heating valve movement: 156.0 Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. HIGH
2 HIGH 88.0 RUNTIME_OPERATION FCU_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 500.98; Total enabled hours: 299.98; Run while disabled hours: 214.0; Enabled not running hours: 13.0; After-hours run hours: 55.02; Total starts: 31; Average daily run hours: 16.7; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. HIGH
3 HIGH 88.0 RUNTIME_OPERATION FCU_03
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 500.98; Total enabled hours: 506.91; Run while disabled hours: 7.11; Enabled not running hours: 13.04; After-hours run hours: 55.03; Total starts: 31; Average daily run hours: 16.7; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. HIGH
4 HIGH 88.0 RUNTIME_OPERATION FCU_04
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 393.47; Total enabled hours: 429.96; Run while disabled hours: 53.53; Enabled not running hours: 90.02; After-hours run hours: 64.23; Total starts: 319; Average daily run hours: 13.12; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. HIGH
5 HIGH 88.0 RUNTIME_OPERATION FCU_05
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 500.97; Total enabled hours: 506.95; Run while disabled hours: 7.08; Enabled not running hours: 13.06; After-hours run hours: 55.02; Total starts: 31; Average daily run hours: 16.7; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. HIGH
6 HIGH 88.0 COMFORT_CONTROL FCU_05
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05
COOLING_NOT_EFFECTIVE
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 10.5; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 26.5; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 3145.0; Heating valve movement: 0.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. HIGH
7 HIGH 88.0 RUNTIME_OPERATION FCU_06
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 500.97; Total enabled hours: 31.83; Run while disabled hours: 469.15; Enabled not running hours: 0.0; After-hours run hours: 55.02; Total starts: 30; Average daily run hours: 16.7; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Review schedules and after-hours operation. HIGH
8 HIGH 88.0 COMFORT_CONTROL FCU_06
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06
ZONE_BELOW_SETPOINT
Zone temperature appears below setpoint for part of the sample period.
Thermal score: 30; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 26.25; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 3.25; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 2600.0; Heating valve movement: 0.0 Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. HIGH
9 HIGH 88.0 RUNTIME_OPERATION FCU_07
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 356.47; Total enabled hours: 1.14; Run while disabled hours: 355.42; Enabled not running hours: 0.09; After-hours run hours: 12.59; Total starts: 26; Average daily run hours: 11.88; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Review schedules and after-hours operation. HIGH
10 HIGH 88.0 COMFORT_CONTROL FCU_07
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07
HEATING_NOT_EFFECTIVE
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 0; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 30.0; Zone below setpoint hours: 24.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 1.0; Heating valve open supply not warm hours: 9.0; Cooling valve movement: 313.0; Heating valve movement: 2127.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. HIGH
11 HIGH 88.0 RUNTIME_OPERATION FCU_08
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 367.99; Total enabled hours: 368.33; Run while disabled hours: 82.02; Enabled not running hours: 82.35; After-hours run hours: 0.0; Total starts: 30; Average daily run hours: 12.27; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. HIGH
12 HIGH 88.0 COMFORT_CONTROL FCU_08
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08
SIMULTANEOUS_HEAT_COOL
Heating and cooling appear to be active at the same time.
Thermal score: 20; Readiness: PARTIAL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 14.5; Heating valve open supply not warm hours: 66.5; Cooling valve movement: 774.0; Heating valve movement: 991.0 Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. HIGH
13 HIGH 88.0 RUNTIME_OPERATION FCU_09
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 328.63; Total enabled hours: 367.59; Run while disabled hours: 5.26; Enabled not running hours: 44.22; After-hours run hours: 12.6; Total starts: 258; Average daily run hours: 10.95; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. HIGH
14 HIGH 88.0 COMFORT_CONTROL FCU_09
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09
COOLING_NOT_EFFECTIVE
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 15; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 76.75; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 2169.0; Heating valve movement: 0.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. HIGH
15 HIGH 88.0 RUNTIME_OPERATION FCU_10
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 356.47; Total enabled hours: 367.9; Run while disabled hours: 5.37; Enabled not running hours: 16.79; After-hours run hours: 12.6; Total starts: 26; Average daily run hours: 11.88; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. HIGH
16 HIGH 88.0 RUNTIME_OPERATION FCU_11
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 568.84; Total enabled hours: 475.41; Run while disabled hours: 100.9; Enabled not running hours: 7.46; After-hours run hours: 150.62; Total starts: 58; Average daily run hours: 18.96; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. HIGH
17 HIGH 88.0 COMFORT_CONTROL FCU_11
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11
HEATING_NOT_EFFECTIVE
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 113.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 28.0; Cooling valve movement: 0.0; Heating valve movement: 8539.0 Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. HIGH
18 HIGH 88.0 COMFORT_CONTROL FCU_12
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_12
COOLING_NOT_EFFECTIVE
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 15; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 80.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 93.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 1200.0; Heating valve movement: 0.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. HIGH
19 HIGH 88.0 RUNTIME_OPERATION FCU_13
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 399.61; Total enabled hours: 710.17; Run while disabled hours: 5.63; Enabled not running hours: 316.19; After-hours run hours: 39.29; Total starts: 39; Average daily run hours: 13.32; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. HIGH
20 HIGH 88.0 COMFORT_CONTROL FCU_13
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13
COOLING_NOT_EFFECTIVE
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 38.75; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 6891.0; Heating valve movement: 0.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. HIGH
21 HIGH 88.0 COMFORT_CONTROL FCU_14
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_14
COOLING_NOT_EFFECTIVE
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 5; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 167.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 8.25; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 6844.0; Heating valve movement: 0.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. HIGH
22 HIGH 88.0 COMFORT_CONTROL FCU_15
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15
COOLING_NOT_EFFECTIVE
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 0; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 26.25; Zone below setpoint hours: 7.5; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 14.0; Heating valve open supply not warm hours: 66.5; Cooling valve movement: 774.0; Heating valve movement: 989.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. HIGH
23 HIGH 88.0 RUNTIME_OPERATION FCU_16
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16
RUNNING_WHILE_DISABLED
Equipment appears to have runtime while disabled or not commanded to run.
Total status run hours: 356.48; Total enabled hours: 368.36; Run while disabled hours: 4.91; Enabled not running hours: 16.79; After-hours run hours: 12.62; Total starts: 26; Average daily run hours: 11.88; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. HIGH
24 HIGH 88.0 COMFORT_CONTROL FCU_16
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16
COOLING_NOT_EFFECTIVE
Thermal audit flagged this equipment for comfort or control review.
Thermal score: 15; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 14.25; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 2168.0; Heating valve movement: 0.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. HIGH
25 HIGH 80.0 ENERGY_WASTE CoGen
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/CoGen
KW_KWH_DISAGREE
kW-derived energy and kWh counter usage disagree significantly.
Energy score: 0; Period kWh: 0.0; Estimated kWh from kW: 590.87; kW/kWh difference percent: 100.0; Average kW: 3.52; Max kW: 6.5; Base load kW: 0.0; After-hours ratio: 0.93; Average power factor: 0.0; Average voltage imbalance percent: 0.51; Average current imbalance percent: 35.62 kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. MEDIUM
26 HIGH 80.0 ENERGY_WASTE DB_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_01
KW_KWH_DISAGREE
kW-derived energy and kWh counter usage disagree significantly.
Energy score: 0; Period kWh: 906.8; Estimated kWh from kW: 38979.25; kW/kWh difference percent: 97.67; Average kW: 232.02; Max kW: 236.3; Base load kW: 225.9; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.49; Average current imbalance percent: 0.0 kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. MEDIUM
27 HIGH 80.0 ENERGY_WASTE DB_CP_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_CP_01
KW_KWH_DISAGREE
kW-derived energy and kWh counter usage disagree significantly.
Energy score: 0; Period kWh: 374.4; Estimated kWh from kW: 39223.18; kW/kWh difference percent: 99.05; Average kW: 233.47; Max kW: 236.0; Base load kW: 229.7; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.46; Average current imbalance percent: 0.0 kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. MEDIUM
28 HIGH 80.0 ENERGY_WASTE DB_CP_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_CP_02
KW_KWH_DISAGREE
kW-derived energy and kWh counter usage disagree significantly.
Energy score: 0; Period kWh: 0.0; Estimated kWh from kW: 38935.87; kW/kWh difference percent: 100.0; Average kW: 231.76; Max kW: 234.7; Base load kW: 227.5; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.51; Average current imbalance percent: 0.0 kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. MEDIUM
29 HIGH 80.0 ENERGY_WASTE DB_Cafe
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_Cafe
KW_KWH_DISAGREE
kW-derived energy and kWh counter usage disagree significantly.
Energy score: 0; Period kWh: 6.9; Estimated kWh from kW: 39232.85; kW/kWh difference percent: 99.98; Average kW: 233.53; Max kW: 236.1; Base load kW: 229.4; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.53; Average current imbalance percent: 0.0 kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. MEDIUM
30 HIGH 80.0 ENERGY_WASTE DB_Lift_A
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_Lift_A
KW_KWH_DISAGREE
kW-derived energy and kWh counter usage disagree significantly.
Energy score: 0; Period kWh: 77.9; Estimated kWh from kW: 54.07; kW/kWh difference percent: 30.58; Average kW: 0.32; Max kW: 5.8; Base load kW: 0.1; After-hours ratio: 0.84; Average power factor: 0.0; Average voltage imbalance percent: 0.43; Average current imbalance percent: 10.81 kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. MEDIUM
31 HIGH 80.0 ENERGY_WASTE MSSB_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_01
KW_KWH_DISAGREE
kW-derived energy and kWh counter usage disagree significantly.
Energy score: 0; Period kWh: 940.7; Estimated kWh from kW: 573.88; kW/kWh difference percent: 38.99; Average kW: 3.42; Max kW: 6.5; Base load kW: 0.0; After-hours ratio: 1.0; Average power factor: 0.0; Average voltage imbalance percent: 0.49; Average current imbalance percent: 15.2 kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. MEDIUM
32 HIGH 80.0 ENERGY_WASTE MSSB_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_02
KW_KWH_DISAGREE
kW-derived energy and kWh counter usage disagree significantly.
Energy score: 0; Period kWh: 1861.2; Estimated kWh from kW: 368.35; kW/kWh difference percent: 80.21; Average kW: 2.19; Max kW: 6.6; Base load kW: 0.0; After-hours ratio: 1.18; Average power factor: 0.0; Average voltage imbalance percent: 0.54; Average current imbalance percent: 3.95 kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. MEDIUM
33 HIGH 80.0 ENERGY_WASTE MSSB_03
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_03
KWH_ONLY_USAGE
Energy audit flagged this meter for review.
Energy score: 0; Period kWh: 5.8; Estimated kWh from kW: 0.0; kW/kWh difference percent: 100.0; Average kW: 0.0; Max kW: 0.0; Base load kW: 0.0; After-hours ratio: 0.0; Average power factor: 0.0; Average voltage imbalance percent: 0.29; Average current imbalance percent: 0.0 kWh counter increased while kW-derived usage was zero or unavailable. Check whether true power is disabled, scaled incorrectly, mapped to the wrong point, or not recording useful values. kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. MEDIUM
34 MEDIUM 63.0 COMFORT_CONTROL AHU_05
slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05
THERMAL_DATA_QUALITY
Thermal audit data quality is incomplete or weak for this equipment.
Thermal score: 60; Readiness: LOW_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 0.0 Fallback zone setpoint is available, but zone comfort could not be calculated because zone temperature data was not usable. NONE
35 MEDIUM 63.0 COMFORT_CONTROL Chiller_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02
THERMAL_DATA_QUALITY
Thermal audit data quality is incomplete or weak for this equipment.
Thermal score: 60; Readiness: LOW_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 0.0 Fallback zone setpoint is available, but zone comfort could not be calculated because zone temperature data was not usable. NONE
36 MEDIUM 58.0 COMFORT_CONTROL FCU_03
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03
ZONE_ABOVE_SETPOINT
Zone temperature appears above setpoint for part of the sample period.
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 0.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. HIGH
37 MEDIUM 58.0 COMFORT_CONTROL FCU_04
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04
ZONE_ABOVE_SETPOINT
Zone temperature appears above setpoint for part of the sample period.
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 168.0; Zone below setpoint hours: 0.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.5; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 65.0; Heating valve movement: 0.0 Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. HIGH
38 MEDIUM 58.0 COMFORT_CONTROL FCU_10
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10
ZONE_BELOW_SETPOINT
Zone temperature appears below setpoint for part of the sample period.
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 138.75; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.0; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 0.0; Heating valve movement: 213.0 Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. HIGH
39 MEDIUM 58.0 RUNTIME_OPERATION FCU_15
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15
ENABLED_NOT_RUNNING
Equipment appears enabled but did not prove run during part of the sample.
Total status run hours: 367.99; Total enabled hours: 718.85; Run while disabled hours: 0.26; Enabled not running hours: 351.12; After-hours run hours: 0.0; Total starts: 30; Average daily run hours: 12.27; Has status history: true; Has enable history: true A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. HIGH
40 MEDIUM 53.0 COMFORT_CONTROL FCU_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02
ZONE_BELOW_SETPOINT
Zone temperature appears below setpoint for part of the sample period.
Thermal score: 65; Readiness: FULL_THERMAL_READY; Zone above setpoint hours: 0.0; Zone below setpoint hours: 74.0; Simultaneous heat/cool hours: 0.0; Cooling valve open supply not cold hours: 0.5; Heating valve open supply not warm hours: 0.0; Cooling valve movement: 60.0; Heating valve movement: 0.0 Zone comfort used the fallback zone setpoint slot because no usable zone setpoint history was available. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. MEDIUM
41 MEDIUM 48.0 RUNTIME_OPERATION CHWP_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_01
AFTER_HOURS_RUN
Equipment appears to be running outside normal business hours.
Total status run hours: 251.92; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 95.92; Total starts: 1; Average daily run hours: 8.4; Has status history: true; Has enable history: false A previous status value was carried forward to establish the starting state of the audit window. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. MEDIUM
42 MEDIUM 48.0 RUNTIME_OPERATION CHWP_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02
AFTER_HOURS_RUN
Equipment appears to be running outside normal business hours.
Total status run hours: 338.14; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 56.54; Total starts: 27; Average daily run hours: 11.27; Has status history: true; Has enable history: false A previous status value was carried forward to establish the starting state of the audit window. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. MEDIUM
43 MEDIUM 48.0 RUNTIME_OPERATION FCU_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01
AFTER_HOURS_RUN
Equipment appears to be running outside normal business hours.
Total status run hours: 500.98; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 55.02; Total starts: 30; Average daily run hours: 16.7; Has status history: true; Has enable history: false A previous status value was carried forward to establish the starting state of the audit window. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. MEDIUM
44 MEDIUM 48.0 RUNTIME_OPERATION Fluid_Cooler
slot:/Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler
AFTER_HOURS_RUN
Equipment appears to be running outside normal business hours.
Total status run hours: 45.25; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 7.2; Total starts: 166; Average daily run hours: 1.51; Has status history: true; Has enable history: false No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. MEDIUM
45 MEDIUM 48.0 RUNTIME_OPERATION HWP_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_01
AFTER_HOURS_RUN
Equipment appears to be running outside normal business hours.
Total status run hours: 434.86; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 140.18; Total starts: 18; Average daily run hours: 14.5; Has status history: true; Has enable history: false No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. MEDIUM
46 MEDIUM 48.0 RUNTIME_OPERATION HWP_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_02
AFTER_HOURS_RUN
Equipment appears to be running outside normal business hours.
Total status run hours: 438.36; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 144.87; Total starts: 21; Average daily run hours: 14.61; Has status history: true; Has enable history: false No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. MEDIUM
47 MEDIUM 48.0 RUNTIME_OPERATION HWP_03
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_03
AFTER_HOURS_RUN
Equipment appears to be running outside normal business hours.
Total status run hours: 482.63; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 180.95; Total starts: 1; Average daily run hours: 16.09; Has status history: true; Has enable history: false No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. MEDIUM
48 MEDIUM 48.0 RUNTIME_OPERATION HWP_04
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_04
RUNTIME_DATA_QUALITY
Runtime audit flagged this equipment for review.
Total status run hours: 0.0; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 0.0; Total starts: 0; Average daily run hours: 0.0; Has status history: true; Has enable history: false No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. MEDIUM
49 MEDIUM 48.0 RUNTIME_OPERATION LTS_High_Wall_Split
slot:/Drivers/NiagaraNetwork/Site_Y/points/LTS_High_Wall_Split
NO_STATUS_HISTORY
Equipment cannot be reliably runtime-audited because the status history is missing.
Total status run hours: 0.0; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 0.0; Total starts: 0; Average daily run hours: 0.0; Has status history: false; Has enable history: false Status history is required for runtime analytics. Add or repair the status history. NONE
50 MEDIUM 48.0 RUNTIME_OPERATION PHWP_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_01
AFTER_HOURS_RUN
Equipment appears to be running outside normal business hours.
Total status run hours: 719.83; Total enabled hours: 0.0; Run while disabled hours: 0.0; Enabled not running hours: 0.0; After-hours run hours: 270.0; Total starts: 1; Average daily run hours: 23.99; Has status history: true; Has enable history: false A previous status value was carried forward to establish the starting state of the audit window. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. MEDIUM

Equipment Health Summary

RankEquipmentPriorityScoreFindingsHighMediumPrimary FindingRecommended Next ActionSource Stages
1 FCU_05
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_05
HIGH 88.0 2 2 0 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
2 FCU_06
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_06
HIGH 88.0 2 2 0 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
3 FCU_07
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_07
HIGH 88.0 2 2 0 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
4 FCU_08
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_08
HIGH 88.0 2 2 0 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. STAGE_2_RUNTIME;STAGE_3_THERMAL
5 FCU_09
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_09
HIGH 88.0 2 2 0 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
6 FCU_11
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_11
HIGH 88.0 2 2 0 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
7 FCU_13
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_13
HIGH 88.0 2 2 0 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
8 FCU_16
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_16
HIGH 88.0 2 2 0 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
9 CoGen
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/CoGen
HIGH 80.0 1 1 0 KW_KWH_DISAGREE kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. STAGE_4_ENERGY
10 DB_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_01
HIGH 80.0 1 1 0 KW_KWH_DISAGREE kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. STAGE_4_ENERGY
11 DB_CP_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_CP_01
HIGH 80.0 1 1 0 KW_KWH_DISAGREE kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. STAGE_4_ENERGY
12 DB_CP_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_CP_02
HIGH 80.0 1 1 0 KW_KWH_DISAGREE kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. STAGE_4_ENERGY
13 DB_Cafe
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_Cafe
HIGH 80.0 1 1 0 KW_KWH_DISAGREE kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Base load is high compared with average demand. Review permanent loads, parasitic loads, equipment not shutting down, and standby consumption. STAGE_4_ENERGY
14 DB_Lift_A
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_Lift_A
HIGH 80.0 1 1 0 KW_KWH_DISAGREE kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. STAGE_4_ENERGY
15 MSSB_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_01
HIGH 80.0 1 1 0 KW_KWH_DISAGREE kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Current imbalance detected across phases above the minimum load threshold and duration threshold. Review phase loading, distribution board balance, single-phase loads, CT orientation, and metering configuration. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. STAGE_4_ENERGY
16 MSSB_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_02
HIGH 80.0 1 1 0 KW_KWH_DISAGREE kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. After-hours load is high compared with average load. Review schedules, plant left enabled, lighting operation, tenant loads, and equipment that should be off outside normal hours. Low effective power factor detected. Review power factor correction, large inductive loads, VSD behaviour, and billing exposure if applicable. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. STAGE_4_ENERGY
17 MSSB_03
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/MSSB_03
HIGH 80.0 1 1 0 KWH_ONLY_USAGE kWh counter increased while kW-derived usage was zero or unavailable. Check whether true power is disabled, scaled incorrectly, mapped to the wrong point, or not recording useful values. kWh counter usage and kW-derived usage disagree significantly. Check meter scaling, counter resets, rollover behaviour, units, and history quality. Some current imbalance checks were skipped because average load was below the configured minimum current threshold. STAGE_4_ENERGY
18 FCU_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_01
HIGH 75.0 2 1 1 COOLING_VALVE_HUNTING Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. STAGE_3_THERMAL;STAGE_2_RUNTIME
19 FCU_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_02
HIGH 75.0 2 1 1 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
20 FCU_03
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_03
HIGH 75.0 2 1 1 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
21 FCU_04
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_04
HIGH 75.0 2 1 1 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
22 FCU_10
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_10
HIGH 75.0 2 1 1 RUNNING_WHILE_DISABLED A previous status value was carried forward to establish the starting state of the audit window. A previous enable value was carried forward to establish the starting enable state. Investigate why status shows running while enable is false. Check command mapping, manual overrides, local controls, or failed feedback. Investigate enabled-but-not-running periods. Check faults, safeties, fan proving, VSD permissives, and command/status alignment. Review schedules and after-hours operation. STAGE_2_RUNTIME;STAGE_3_THERMAL
23 FCU_12
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_12
HIGH 75.0 2 1 0 COOLING_NOT_EFFECTIVE Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. STAGE_3_THERMAL;STAGE_2_RUNTIME
24 FCU_14
slot:/Drivers/NiagaraNetwork/Site_Y/points/Ground_Floor_FCUs/FCU_14
HIGH 75.0 2 1 0 COOLING_NOT_EFFECTIVE Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Cooling valve movement suggests possible hunting or unstable control. Review PID tuning, sensor noise, actuator behaviour, deadbands, and control loop sequencing. STAGE_3_THERMAL;STAGE_2_RUNTIME
25 FCU_15
slot:/Drivers/NiagaraNetwork/Site_Y/points/Level_1_FCUs/FCU_15
HIGH 75.0 2 1 1 COOLING_NOT_EFFECTIVE Zone temperature was above setpoint plus deadband for a meaningful period. Check load, cooling availability, valve operation, air delivery, and setpoint assumptions. Zone temperature was below setpoint minus deadband for a meaningful period. Check heating operation, excessive cooling, schedules, and setpoint assumptions. Cooling valve was highly open while supply air was not cold. Check chilled water availability, valve operation, coil performance, sensor calibration, and control sequencing. Heating valve was highly open while supply air was not warm. Check hot water availability, valve operation, coil performance, sensor calibration, and control sequencing. Cooling valve was highly open while the zone remained above setpoint. Check cooling capacity, airflow, chilled water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. Heating valve was highly open while the zone remained below setpoint. Check heating capacity, airflow, hot water availability, valve authority, coil condition, sensor calibration, and whether the fallback setpoint is appropriate. STAGE_3_THERMAL;STAGE_2_RUNTIME
26 AHU_05
slot:/Drivers/NiagaraNetwork/Site_Y/points/Pool_Hall_Air/AHU_05
MEDIUM 63.0 1 0 1 THERMAL_DATA_QUALITY Fallback zone setpoint is available, but zone comfort could not be calculated because zone temperature data was not usable. STAGE_3_THERMAL
27 Chiller_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_02
MEDIUM 63.0 1 0 1 THERMAL_DATA_QUALITY Fallback zone setpoint is available, but zone comfort could not be calculated because zone temperature data was not usable. STAGE_3_THERMAL
28 CHWP_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_01
MEDIUM 48.0 1 0 1 AFTER_HOURS_RUN A previous status value was carried forward to establish the starting state of the audit window. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. STAGE_2_RUNTIME
29 CHWP_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/CHWP_02
MEDIUM 48.0 1 0 1 AFTER_HOURS_RUN A previous status value was carried forward to establish the starting state of the audit window. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. STAGE_2_RUNTIME
30 Fluid_Cooler
slot:/Drivers/NiagaraNetwork/Site_Y/points/Fluid_Cooler
MEDIUM 48.0 1 0 1 AFTER_HOURS_RUN No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. Review short cycling, control deadbands, minimum run/off timers, unstable sensors, and command logic. STAGE_2_RUNTIME
31 HWP_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_01
MEDIUM 48.0 1 0 1 AFTER_HOURS_RUN No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. STAGE_2_RUNTIME
32 HWP_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_02
MEDIUM 48.0 1 0 1 AFTER_HOURS_RUN No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. STAGE_2_RUNTIME
33 HWP_03
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_03
MEDIUM 48.0 1 0 1 AFTER_HOURS_RUN No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. STAGE_2_RUNTIME
34 HWP_04
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/HWP_04
MEDIUM 48.0 1 0 1 RUNTIME_DATA_QUALITY No known status value existed at the start of the audit window. Early-window runtime may be incomplete. Add enable history to support enabled-vs-disabled runtime analytics. STAGE_2_RUNTIME
35 LTS_High_Wall_Split
slot:/Drivers/NiagaraNetwork/Site_Y/points/LTS_High_Wall_Split
MEDIUM 48.0 1 0 1 NO_STATUS_HISTORY Status history is required for runtime analytics. Add or repair the status history. STAGE_2_RUNTIME
36 PHWP_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_01
MEDIUM 48.0 1 0 1 AFTER_HOURS_RUN A previous status value was carried forward to establish the starting state of the audit window. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. STAGE_2_RUNTIME
37 PHWP_02
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_02
MEDIUM 48.0 1 0 1 AFTER_HOURS_RUN A previous status value was carried forward to establish the starting state of the audit window. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. STAGE_2_RUNTIME
38 PHWP_03
slot:/Drivers/NiagaraNetwork/Site_Y/points/HW_System/PHWP_03
MEDIUM 48.0 1 0 1 AFTER_HOURS_RUN A previous status value was carried forward to establish the starting state of the audit window. Add enable history to support enabled-vs-disabled runtime analytics. Review schedules and after-hours operation. STAGE_2_RUNTIME
39 Chiller_01
slot:/Drivers/NiagaraNetwork/Site_Y/points/CHW_System/Chiller_01
LOW 30.0 1 0 0 ENERGY_DATA_QUALITY Energy meter histories analysed. No major energy issue detected from available data. STAGE_4_ENERGY
40 DB_Lift_B
slot:/Drivers/NiagaraNetwork/Site_Y/points/Energy_Meters/DB_Lift_B
LOW 30.0 1 0 0 HIGH_AFTER_HOURS_LOAD Some current imbalance checks were skipped because average load was below the configured minimum current threshold. STAGE_4_ENERGY

Stage 10 v0.1 is a master reducer. It reads existing stage outputs and ranks findings. It does not directly read histories, alarms, or BACnet services.