    "row": 5,
    "equipment": "VAV_N2_1",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 9,
    "equipment": "VAV_C2_1",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 17,
    "equipment": "VAV_C2_10",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 18,
    "equipment": "VAV_C2_11",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 22,
    "equipment": "VAV_N3_1",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 23,
    "equipment": "VAV_N3_2",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 24,
    "equipment": "VAV_W3_1",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 29,
    "equipment": "VAV_C3_4",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 32,
    "equipment": "VAV_C3_7",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 33,
    "equipment": "VAV_C3_8",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 34,
    "equipment": "VAV_C3_9",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 35,
    "equipment": "VAV_C3_10",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 36,
    "equipment": "VAV_E3_1",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 38,
    "equipment": "VAV_S3_2",
    "rule": "rule_12",
    "message": "Extreme Cooling Demand (\u2265100%)",
    "priority": "High",
    "action": "Investigate load, coil capacity, and valve control.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 17,
    "equipment": "VAV_C2_10",
    "rule": "rule_5",
    "message": "Setpoint_Deviation \u2265 1.8",
    "priority": "Normal",
    "action": "Check for overshoot/undershoot causes and retune loops.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 23,
    "equipment": "VAV_N3_2",
    "rule": "rule_5",
    "message": "Setpoint_Deviation \u2265 1.8",
    "priority": "Normal",
    "action": "Check for overshoot/undershoot causes and retune loops.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 8,
    "equipment": "VAV_W2_2",
    "rule": "rule_57",
    "message": "Damper output is zero with airflow greater than 60 L/s.",
    "priority": "High",
    "action": "Check for stuck damper and inspect air handling unit.",
    "notify": "maintenance_team",
    "active": true
  },
  {
    "row": 34,
    "equipment": "VAV_C3_9",
    "rule": "rule_57",
    "message": "Damper output is zero with airflow greater than 60 L/s.",
    "priority": "High",
    "action": "Check for stuck damper and inspect air handling unit.",
    "notify": "maintenance_team",
    "active": true
  },
  {
    "row": 5,
    "equipment": "VAV_N2_1",
    "rule": "rule_59",
    "message": "Setpoint deviation is higher than 1.3 degrees.",
    "priority": "Normal",
    "action": "Check for overactive heating or cooling elements.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 17,
    "equipment": "VAV_C2_10",
    "rule": "rule_59",
    "message": "Setpoint deviation is higher than 1.3 degrees.",
    "priority": "Normal",
    "action": "Check for overactive heating or cooling elements.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 23,
    "equipment": "VAV_N3_2",
    "rule": "rule_59",
    "message": "Setpoint deviation is higher than 1.3 degrees.",
    "priority": "Normal",
    "action": "Check for overactive heating or cooling elements.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 34,
    "equipment": "VAV_C3_9",
    "rule": "rule_59",
    "message": "Setpoint deviation is higher than 1.3 degrees.",
    "priority": "Normal",
    "action": "Check for overactive heating or cooling elements.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 35,
    "equipment": "VAV_C3_10",
    "rule": "rule_59",
    "message": "Setpoint deviation is higher than 1.3 degrees.",
    "priority": "Normal",
    "action": "Check for overactive heating or cooling elements.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 36,
    "equipment": "VAV_E3_1",
    "rule": "rule_59",
    "message": "Setpoint deviation is higher than 1.3 degrees.",
    "priority": "Normal",
    "action": "Check for overactive heating or cooling elements.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 38,
    "equipment": "VAV_S3_2",
    "rule": "rule_59",
    "message": "Setpoint deviation is higher than 1.3 degrees.",
    "priority": "Normal",
    "action": "Check for overactive heating or cooling elements.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 24,
    "equipment": "VAV_W3_1",
    "rule": "rule_6",
    "message": "Velocity_Pressure \u2264 0",
    "priority": "Normal",
    "action": "Inspect pitot/sensor plumbing; confirm fan and duct integrity.",
    "notify": "maintenance_team",
    "active": true
  },
  {
    "row": 24,
    "equipment": "VAV_W3_1",
    "rule": "rule_62",
    "message": "Velocity pressure is at or below 4 units.",
    "priority": "Normal",
    "action": "Assess airflow dynamics and adjust fan speeds.",
    "notify": "maintenance_team",
    "active": true
  },
  {
    "row": 34,
    "equipment": "VAV_C3_9",
    "rule": "rule_62",
    "message": "Velocity pressure is at or below 4 units.",
    "priority": "Normal",
    "action": "Assess airflow dynamics and adjust fan speeds.",
    "notify": "maintenance_team",
    "active": true
  },
  {
    "row": 29,
    "equipment": "VAV_C3_4",
    "rule": "rule_63",
    "message": "Airflow exceeds the maximum specified for cooling.",
    "priority": "Normal",
    "action": "Reduce airflow to within specified cooling parameters.",
    "notify": "operations_manager",
    "active": true
  },
  {
    "row": 33,
    "equipment": "VAV_C3_8",
    "rule": "rule_63",
    "message": "Airflow exceeds the maximum specified for cooling.",
    "priority": "Normal",
    "action": "Reduce airflow to within specified cooling parameters.",
    "notify": "operations_manager",
    "active": true
  },
  {
    "row": 36,
    "equipment": "VAV_E3_1",
    "rule": "rule_63",
    "message": "Airflow exceeds the maximum specified for cooling.",
    "priority": "Normal",
    "action": "Reduce airflow to within specified cooling parameters.",
    "notify": "operations_manager",
    "active": true
  },
  {
    "row": 24,
    "equipment": "VAV_W3_1",
    "rule": "rule_64",
    "message": "Cooling demand is present but airflow is below minimum cooling flow setpoint.",
    "priority": "High",
    "action": "Increase airflow to meet cooling demands.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 34,
    "equipment": "VAV_C3_9",
    "rule": "rule_64",
    "message": "Cooling demand is present but airflow is below minimum cooling flow setpoint.",
    "priority": "High",
    "action": "Increase airflow to meet cooling demands.",
    "notify": "facility_team",
    "active": true
  },
  {
    "row": 29,
    "equipment": "VAV_C3_4",
    "rule": "rule_67",
    "message": "Heating demand is low yet airflow exceeds the maximum cooling flow setpoint.",
    "priority": "High",
    "action": "Reduce airflow to prevent overheating.",
    "notify": "maintenance_team",
    "active": true
  },
  {
    "row": 33,
    "equipment": "VAV_C3_8",
    "rule": "rule_67",
    "message": "Heating demand is low yet airflow exceeds the maximum cooling flow setpoint.",
    "priority": "High",
    "action": "Reduce airflow to prevent overheating.",
    "notify": "maintenance_team",
    "active": true
  },
  {
    "row": 36,
    "equipment": "VAV_E3_1",
    "rule": "rule_67",
    "message": "Heating demand is low yet airflow exceeds the maximum cooling flow setpoint.",
    "priority": "High",
    "action": "Reduce airflow to prevent overheating.",
    "notify": "maintenance_team",
    "active": true
  },
  {
    "row": 29,
    "equipment": "VAV_C3_4",
    "rule": "rule_7",
    "message": "Supply_Air_Flow greater than Cooling_Max_Flow_SP",
    "priority": "Normal",
    "action": "Clamp airflow to max cooling spec.",
    "notify": "operations_manager",
    "active": true
  },
  {
    "row": 33,
    "equipment": "VAV_C3_8",
    "rule": "rule_7",
    "message": "Supply_Air_Flow greater than Cooling_Max_Flow_SP",
    "priority": "Normal",
    "action": "Clamp airflow to max cooling spec.",
    "notify": "operations_manager",
    "active": true
  },
  {
    "row": 36,
    "equipment": "VAV_E3_1",
    "rule": "rule_7",
    "message": "Supply_Air_Flow greater than Cooling_Max_Flow_SP",
    "priority": "Normal",
    "action": "Clamp airflow to max cooling spec.",
    "notify": "operations_manager",
    "active": true
  }
]